Instruction Manual

Repeater Hubs

Summary of Contents for EORP-200

Page 1: ...Instruction Manual Repeater Hubs ...

Page 2: ...are considering a special use of this product Incorporate and install failsafe functions emergency stop monitoring and similar devices if using this product in equipment that could cause a serious accident or loss About Disposal When disposing this product follow the rules and regulations of the corresponding local government and dispose of it as industrial waste 2021 Nabeya Bi tech Kaisha Co Ltd ...

Page 3: ...tion Manuals for Wired Wireless Positioning Units Prepare the following manuals according to the products you have purchased All of the following PDF instruction manuals can be downloaded from our product page https www nbk1560 com en US products mechatronics positioning_unit Wired Wireless positioning units EPU 220 EPU 210 ...

Page 4: ...nt 10 2 4 Block Diagram 11 3 Specifications 12 4 Installation and Connections 14 4 1 Installation Requirements 14 4 2 Repeater Hub Installation 15 4 2 1 Main Unit Installation 15 4 2 2 Connector Installation 16 4 2 3 Power Supply Wiring 17 4 2 4 Extending Cables for Repeater Hubs 18 4 3 Connections 20 5 Maintenance 22 5 1 Precautions for Inspection 22 5 2 Inspection Checklist 22 6 Troubleshooting ...

Page 5: ...r a third party failures that occur during use other defects or damages caused by the use of this product Safety precautions in this manual are classified as indicated below in order to prevent personal damage and damage to the units and peripheral equipment Specific safety precautions are indicated in written form near each WARNING and CAUTION symbol WARNING Indicates that improper handling can l...

Page 6: ...t the product Be sure to securely install the protective cover after connecting the power supply terminals Ensure that wiring work is performed after installation and the power supply terminal connections are properly insulated Be sure to install an external emergency stop circuit so that operation is immediately stopped and the power is shut off in the event of an abnormality PROHIBITED Prohibite...

Page 7: ...to Prevent Other Damage When attaching a connector into the repeater hub pay attention to the position of the notches to fit in insert it straight and securely and ensure that the screws are not loose Be sure to disconnect the power cable and connectors when moving the repeater hub Install the product in a location that allows an appropriate work space for operation adjustment and maintenance PROH...

Page 8: ...f the power supply and do not turn it back on Do not move inspect or perform wiring work while the product power is on Do not handle flammable gas in the vicinity of the product Do not operate with wet hands CAUTION COMPULSORY INSTRUCTION Perform as Indicated in Order to Prevent Injury and Failure Be sure to turn off the power if you plan on not using the product for an extended period of time PRO...

Page 9: ...host PC PLC or a transceiver to other ports wired wireless positioning units Optional Cables for Repeater Hubs EOCA 200 A Cables which connect repeater hubs to the host PC PLC or the transceivers It is possible to connect to a USB port on your PC via a serial converter Cables for Repeater Hubs EOCA 200 B Cables which connect two different repeater hubs Cables for Repeater Hubs EOCA 200 C Extension...

Page 10: ...terminal block protective cover Used to protect the power supply terminals Power supply terminal block Used to connect the power supply terminals Power lamp Indicates whether the power is supplied Pin No Name Description EPU 210 EPU 220 1 ー ー ー 2 D CA RS 485communicationsignal A 3 DG CS RS 485 GND Shield 4 D CB RS 485communicationsignal B SLD ー ー ー Pin No Name Description EPU 210 EPU 220 1 ー ー ー 2...

Page 11: ...ignal Name EPU 210 ー D DG D EPU 220 ー CA CS CB Cable length 2 2 m 6 6 ft 5 5 m 16 ft Connected devices A Host transceiver repeater hub B Repeater hub repeater hub C Repeater hub wired wireless positioning unit Series name EOCA 200 Cables for Repeater Hubs 3 4 2 1 CN1 CN2 Loose wires 3 wires Cable terminal Ferrule terminals M12 D code 4 pin shielded female White Green D CA Green D CB Orange DG CS 3...

Page 12: ... Diagram 4 3 1 2 4 3 1 2 CN1 CN2 M12 A code 4 pin shielded female M12 A code 4 pin shielded male Repeater Hubs EORP 200 Isolation COM A connector Power supply terminal block COM B connector EPU connector 8 ports M12 D code 4 p male 24 VDC 0 V FG M12 D code 4 p female M12 A code 4 p female RS 485 driver RS 485 driver RS 485 driver ...

Page 13: ...ode 4 pin shielded female External dimensions 86 mm x 190 mm x 51 2 mm 3 386 in x 7 48 in x 2 016 in Mass 330 g 11 64 oz Cable for Repeater Hubs EOCA 200 A Product No EOCA 200 A 2 EOCA 200 A 5 Cable Shielded movable cable Sheath material PUR Sheath outer diameter 6 4 mm 0 2 mm 0 252 in 0 008 in Number of core wires 2P Conductor cross sectional area AWG26 Cable terminal CN1 Ferrule terminals CN2 M1...

Page 14: ...1 024 in Movable installation 52 mm 2 047 in Cable length 2 m 6 6 ft 5 m 16 ft Mass 119 g 4 2 oz 242 g 8 54 oz EOCA 200 C Product No EOCA 200 C 2 EOCA 200 C 5 Cable Shielded movable cable Sheath material PUR Sheath outer diameter 6 4 mm 0 2 mm 0 252 in 0 008 in Number of core wires 2P Conductor cross sectional area AWG26 Cable terminal CN1 M12 A code 4 pin shielded male CN2 M12 A code 4 pin shield...

Page 15: ...re to water or oil An environment that facilitates the dissipation of heat A place that allows easy inspection and cleaning A location with an ambient temperature ranging from 5 to 55 23 to 131 no freezing and an ambient humidity ranging from 20 to 85 RH no condensation Avoid environments where it may be exposed to water corrosive atmosphere flammable gas harmful gas or near flammable materials Ca...

Page 16: ...s into the surface on which you wish to mount the repeater hub 2 Mount the product using the Main unit mounting holes and the four included Hex socket head cap screws M3 8 Recommended tightening torque 0 3 N m 2 65 lbf in 4 M3x0 5 Effective screw depth 4 0 157 or more 179 5 7 067 60 2 362 Unit mm in Main unit mounting hole Hex socket head cap screw ...

Page 17: ...hes and insert the connector straight into the repeater hub 2 Secure the connection by tightening the Knurled knob at the end of the connector on the cable Tighten the knurled knob by hand until it is finger tight Do not use a tool such as pliers Notches Knurled knob CAUTION COMPULSORY INSTRUCTION ...

Page 18: ...illips head screw Recommended tightening torque 1 2 N m 10 6 lbf in Do not use excessive force when tightening the Phillips head screw 3 Attach the Protective cover to the power supply terminal block Ensure that the protective cover is installed to prevent an electrical leakage or a short circuit Protective cover Power supply terminal Phillips head screw CAUTION Protective cover CAUTION COMPULSORY...

Page 19: ...low Extension of EOCA 200 A Use EOCA 200 B when extending EOCA 200 A Extension of EOCA 200 B Use EOCA 200 B when extending EOCA 200 B Extension of EOCA 200 C Use EOCA 200 C when extending EOCA 200 C Be sure to use the cables for a repeater hub with a maximum extension of less than 30 m 98 ft EOCA 200 A Connect EOCA 200 B EOCA 200 B Connect EOCA 200 B EOCA 200 C unit Connect EOCA 200 C ...

Page 20: ...ion of the Notches and insert the cable connectors in a straight direction 2 Secure the connection by tightening the Knurled knob at the end of the connector Tighten the knurled knob by hand until it is finger tight Do not use a tool such as pliers Notches Knurled knob CAUTION COMPULSORY INSTRUCTION ...

Page 21: ...sistor 120 Ω between communication line terminals D and D on the serial converter side Be sure to use the cables for a repeater hub with a maximum extension of less than 30 m 98 ft Refer to P 18 D D DG D D DG D D DG D D DG D D DG 24V 0V 24V 0V D D DG 24V 0V EPU 210 B 3 EPU 210 B 3 Repeater hubs EORP 200 Serial converter COM A connector COM B connector EPU connector 1 3 EPU connector 2 3 Power supp...

Page 22: ...e Be sure to use the cables for a repeater hub with a maximum extension of less than 30 m 98 ft Refer to P 18 SDA SDB SG RDB RDA Terminating resistor 120 Ω PLC D D DG D D DG D D DG D D DG D D DG D D DG 24V 0V 24V 0V 24V 0V EPU 210 B 2 EPU 210 B 2 Repeater hubs EORP 200 COM A connector COM B connector EPU connector 1 2 EPU connector 1 2 EPU connector 2 2 Power supply terminal block FG 24V 0V Cables...

Page 23: ...sure to carry out the following inspections periodically to prevent accidents 5 2 Inspection Checklist Is the power supply voltage within the specified range Is the operating environment within the specification ranges Is there any abnormal odor or heat generation Is there adhesion of dust or other foreign material Does the power supply or a connector have a loose connection Is any cable damaged o...

Page 24: ...e correct Make sure the voltage level is within 24 V 10 P 12 Is the power supply cable connected correctly Wire correctly P 17 Units wired communication is not possible Is the connector properly connected correctly Ensure it is correctly set and connected P 16 P 18 Is the terminating resistor correctly set and connected P 20 P 21 ...

Page 25: ...24 EORP 200 Unit mm in 51 2 2 016 179 5 7 067 5 25 0 207 13 0 512 190 7 48 35 1 378 7 0 276 170 6 693 86 3 386 60 2 362 7 Dimensional Outline Drawings ...

Page 26: ... are for general industrial use and cannot be used in principle because they are not planned or designed for the following applications that require a high level of safety 1 Medical equipment related to the maintenance and management of human life and body 2 Mechanisms and mechanical devices for the purpose of moving or transporting people vehicles railroad facilities aviation facilities etc 3 Imp...

Page 27: ...eclaration We hereby declare under our sole responsibility that the following product is in conformity with the relevant Union harmonisation legislation From the following terms EMC Directive 2014 53 EU RoHS Directive EU 2015 863 Product Name Repeater Hubs Model Name EORP 200 Manufacturer Name Nabeya Bi tech Kaisha Add 1 Toko Taichi Seki City Gifu 501 3939 Japan The full text of the EU declaration...

Page 28: ... used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense 9 3 Canada ISED This device complies with Industry Canada license exempt RSS standard s Operation is subject to the foll...

Page 29: ...28 9 Laws and regulations 9 4 Korea KCC 인증번호 R R NbK EORP 200 사용자 안내문 이 기기는 업무용 환경에서 사용할 목적으로 적합성평가를 받은 기기로서 가정용 환경에서 사용하는 경우 전파간섭의 우려가 있습니다 ...

Page 30: ...the issue related to the claim was caused by usage outside of the product specifications When the issue related to the claim was caused by fire earthquake lightning wind and flood damage salt damage abnormal power supply voltage or any other man made or natural disaster When the issue related to the claim was caused by exposure to water oil fragments of metal or other foreign materials This warran...

Page 31: ...30 Revision History Date ID No Revision Details Feb 2022 UM EORP200 SU 01E First edition ...

Page 32: ...First edition Feb 2022 UM EORP200 SU 01E ...