- 8 -
Do not tighten the terminals without an inserted wire.
This may damage the clamping mechanism or the plastic
cover of the termina.
7. Additional pulse receiver connected to terminals 20(+) – 21(–).
The terminals are located under the top shell meter terminals.
Additional pulse receiver is not required.
8. Pull the cap setting button transmission. Program indicator.
Slide the cap.
The housing has a hole for safety seal assumption.
9. Put the meter terminals covers.
installation 4-wire
rated voltage
3×230/400 V
minimum measured current
0.04 A
base current
1.5 A
maximum current
6 A
secondary current transformer
5 A
voltage measuring range
160÷265 V AC
measurement accuracy (IEC62052)
1st class
rated frequency
50 Hz
insulation protection class
II
housing
PC material
own power consumption
10 VA; 0.2 W
load capacity of current inputs
0.4 VA
Technical data