- 17 -
DMM-5T-3 User manual
Parameter
number
Parameter
Unit
Factory
value
Minimum value
Maximum value
Ctr
Current transformer ratio
–
1
1
5000
Vtr
Voltage transformer ratio
–
1.0
0.1
999.9
br
Baudrate
bps
9600
1200
115200
–
Stop bits
–
1
–
–
–
Data bits
–
8
–
–
–
Parity
–
none
–
–
Id
Modbus ID
–
1
1
247
En
Deleting total energy
–
no
yes
no
dE
Deleting demand values
–
no
yes
no
LO
Deleting event records
–
no
yes
no
PASS
Password
–
0
0
9999
Con Type
Connection type
–
3P4L
3P4L
3P4L
Date set
Date
–
–
2000
2100
Time set
Hour
–
–
–
–
Par
Parameter
–
OFF
OFF, Uln, Iln, Ilt, thdU,
thdI, PF, U Un, I Un, dI n
Fun
Function
–
high
high
low
UAL
Uln (voltage)
Volt
vtr×10
vtr×10
vtr×500
Iln (current)
Amper
(ctr×10)/100
(ctr×10)/100
(ctr×500)/100
Ilt (total current)
Amper
(ctr×3×10)/100 (ctr×3×10)/100 (ctr×3×500)/100
thdU (total voltage har.)
%
1
1
50
thdI (total current har.)
%
1
1
50
PF (power factor)
%
0.50
0.50
0.99
U Un (voltage imbalance)
%
1
1
50
I Un (current imbalance)
%
1
1
50
Dip
Low voltage
%
<Vtr × 230 × 0.90 ve <Vtr × 400 × 0.90
Swl
High voltage
%
>Vtr × 230 × 1.10 ve >Vtr × 400 × 1.10
Cut
No voltage
%
<Vtr × 230 × 0.40 ve <Vtr × 400 x 0.40
Lmt I
Current limit
%
>Ctr × 0.80
Lmt Thd-V Thd-V limit
%
>1.20
Lmt Thd-I
Thd-I limit
%
>1.20
Lmt PF
Power factor limit
%
<0.80
Dl n
Data input frequency
Hz
>1 Hz
13. Menu values table
Summary of Contents for DMM-5T-3