Lumina 38
Installer
35
Con.
/
Con. Extra
/
Mod. %
The entry depends on the system setting
M/MT-part
in
HOUSE SETUP
, tab page
Combi
:
•
Con.
Enter the positions of the linear controllable fans.
•
Con. Extra
(This column is only active if extra fans are used in the controllable part)
Control of extra fan
Settings: Position 0-R for relay
Setting: Position 0-A for linear
•
Mod. %
(This column is only present if modulating fans are used)
The control computer uses the set ventilation percentage to calculate the on and off
times for the modulating fans.
Relay
0 = fan off
1 = fan on
M = modulating fan (This option is only possible if modulating fans are used)
INSTALLER
→
VENTILATION
→
COMBI MTT
→
M/MT-phase(min)
→
tab page
Inlet
Position %
Setting of the ventilation percentage at which fans should activate/deactivate and air
inlets open/close. The ventilation percentages must increase from the lowest to the
highest position.
Inlet %
Setting of the required inlet positions.
Tunnel %
Setting of the required inlet positions. (If the tunnel inlet is not used, you may enter the
summer inlet position at tunnel inlet position.)
Pressure Pa
Setting of the required pressure for the corresponding position. A rule of thumb: the
higher the ventilation position, the lower the required pressure. Enter 0 to deactivate
pressure control.
Summary of Contents for LUMINA 38
Page 1: ...g...