Lumina 38
Explanation control functions
7
Example: Taking ventilation positions from the combi-table
The required ventilation level on a certain day is 21%.
The control computer uses the settings at position M3:
•
Controllable fans and the extra controllable fans: 25% activated.
•
Contr./Extra fans: deactivated.
•
One Exhaust relay fan activated.
•
Air inlets: 21% open.
•
Tunnel inlets: Do not use.
Example: Settings between two positions
The required ventilation level is 28%. This percentage is between positions M3 and M4. The control
computer uses the following settings:
•
Controllable fans and the extra controllable fans: 62% activated.
•
Contr./Extra fans: deactivated.
•
One Exhaust relay fan activated.
•
Air inlets: 28% open (midway between M3 and M4).
•
Tunnel inlets: Do not use.