Lumina 16
Inputs and outputs
56
Max. buffer
The control computer repeatedly determines the difference between the actual control
value and the required setpoint. It places these difference values in a buffer, until the
Max. buffer
is reached.
The adjustment to the setpoint is the average of the values in the buffer. The control
computer can correct the adjustment using the
Correction factor
.
Min.jump…max
The control range of the analog output. Enter the minimum and maximum jump (in %).
Actual value
Shows the actual value of the control voltage of the analog output.
Digital outputs have the following settings:
Output address
The address of the output.
Channel type
Shows the type of relay being used
NONE
ON/OFF
MODULATING
OPEN/O/CLOSE
LINKED
Channel function
Setting of the type of digital control
DIRECT
HEATING
COOLING
Hysteresis
With an on/off control this is the switch difference of the relay control.
With a modulating control this is the switch range of the relay control.
Repeat time
With on/off control this is the minimum time the relay is active/inactive. With a
modulating on/off control the control computer takes the modulation time from this time.
Max buffer
Always set to 0 with relay.
Actual value
Shows the actual relay status.