Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD3N-L Series User Manual V1.0
- 37
-
Ref. Code
Function Description
Setting Range [Default]
2,3: UP/DN.
•
Set control terminal to control up and down of elevator. The terminals are in below table.
UP Terminal (No.2)
DN Terminal (No.3)
Elevator status
0
0
Stop
0
1
Down
1
0
Up
1
1
Stop
123
4 - 6: Multi-speed 1 - 3 (MS1 - MS3).
•
Achieve 8-speed running curve via terminals logic combination, as follow table.
MS3 Terminal (No.6) MS2 Terminal (No.5) MS13 Terminal (No.4)
Multi-speed Setting
0
0
0
Multi-speed 0 (F05.00)
0
0
1
Multi-speed 1 (F05.01)
0
1
0
Multi-speed 2 (F05.02)
0
1
1
Multi-speed 3 (F05.03)
1
0
0
Multi-speed 4 (F05.04)
1
0
1
Multi-speed 5 (F05.05)
1
1
0
Multi-speed 6 (F05.06)
1
1
1
Multi-speed 7 (F05.07)
123
7: Inspection input (INS).
•
If enabled, elevator will do inspection running.
•
This signal, when used together with UP/DN (No.2 or No.3 function) command, can control the elevator
to go up or down during inspection.
8: Emergency run input (BAT).
•
If enabled, elevator will enter emergency running status.
9: Run contactor feedback input (CSM).
10: Brake feedback input (BSM).
11 - 14: Unused.
15: Motor overheat input (OH).
16: Fault reset input (RST).
•
When HD3N-L alarms fault, reset it by this terminal.
•
The function of RST terminal is the same as the
(standard) or
STOP
(optional) of the keypad.
17 - 33: Unused.
34: External fault (EXT).
•
The fault signal of external equipment can input through this terminal, so HD3N-L can monitor that
equipment and respond accordingly. HD3N-L alarms E0024 (external fault) when receives the EXT
signal.
F12.13
Filter time of multi-speed terminal
0.000 - 2.000 [0.010s]
Defines the MS filter time to make up for the time error of MS input terminals.
•
Change F12.13 according to the change unsynchronization level of numbers of MS input terminals.
6