background image

1.4 GAS SUPPLY

The incoming service must be of sufficient size to supply

full rate gas without excessive pressure drop. A gas meter

is connected to the service pipe by Gas Supplier.

Any existing meter should be checked by the supplier to

ensure that it is of adequate capacity to pass required

rate of gas for the unit, in addition to any other gas

equipment that has been installed.

The multifunctional control has an in-built governor

therefore an external device does not require to be fitted.

Installation pipework should be fitted in accordance with

IGE/UP/2. This should not be smaller than gas inlet

connection.

G3830

- Rp½ 

(½" BSP) 

G3860

- Rp¾ 

(¾" BSP)

G3865

- 2 x Rp½ 

(½" BSP)

An inlet manifold may be purchased to connect G3865 to

1 x Rp¾ 

(¾" BSP)

mains inlet.

An isolating cock must be located close to the unit to

allow shutdown during an emergency or servicing.

The installation should be checked for gas tightness and

purged as specified in IGE/UP/1.

1.5 ELECTRICAL SUPPLY

Not applicable to these units.

1.6 WATER SUPPLY

Not applicable to these units.

1.7 TOTAL GAS RATES - 

NATURAL and PROPANE GAS

1.1 MODEL NUMBERS, NETT WEIGHTS 

and DIMENSIONS

1.2 SITING

The unit should be installed on a level, fireproof surface

in a well lit, draught free position. A clear space of 150mm

should be left between the rear and sides of the fryer and

any combustible wall.

If the floor is constructed of combustible material,

then local fire requirements should be checked to ensure

compliance. 

Important

If appliance is to be installed in suite formation with other

matching units, the instructions for all models must be

consulted to determine the necessary clearances to any

combustible rear wall or overlying surface. Some models

require greater clearances than others and the largest

figure quoted in individual instructions will therefore

determine clearance of complete suite adjoining

appliances. 

1.3 VENTILATION

Adequate ventilation must be provided to supply sufficient

fresh air for combustion. This should allow easy removal

of combustion products which may be harmful to health.

Recommendations for Ventilation of Catering Appliances

are given in BS5440:2. 

For multiple installations, the requirements for individual

units require to be added together. Installation should be

carried out in accordance with local and/or national

regulations which apply at the time. A competent installer

MUST be employed.

Model

Width

(mm)

Depth

(mm)

Height

(mm)

Weight

(kg)

G3830 Fryer

300

770

870

59

G3860 Fryer

600

770

870

74

G3865 Fryer

600

770

870

99

SECTION 1 - INSTALLATION

UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER 

ARE NOT TO BE ADJUSTED BY THE INSTALLER.

Model

kW

Btu/hr

G3830 Fryer

18.1

61,757

G3860 Fryer

32.5

110,890

G3865 Fryer

2 x 18.1

2 x 61,757

Summary of Contents for G3830

Page 1: ...to the User having had a demonstration of the operation and cleaning of the Appliance IT IS MOST IMPORTANT THAT THESE INSTRUCTIONS BE CONSULTED BEFORE INSTALLING AND COMMISSIONING THIS APPLIANCE FAILURE TO COMPLY WITH THE SPECIFIED PROCEDURES MAY RESULT IN DAMAGE OR THE NEED FOR A SERVICE CALL PREVENTATIVE MAINTENANCE CONTRACT In order to obtain maximum performance from this unit we would recommen...

Page 2: ...ion systems Gas water and electrical supply external to unit Light bulbs Re installing vacuum in kettle jackets Replacement of grill burner ceramics when damage has been clearly caused by misuse Where an engineer finds no fault with a product that has been reported faulty Re setting or adjustment of thermostats when unit is operating to specification Cleaning and unblocking of fryer filter systems...

Page 3: ...between the rear and sides of the fryer and any combustible wall If the floor is constructed of combustible material then local fire requirements should be checked to ensure compliance Important If appliance is to be installed in suite formation with other matching units the instructions for all models must be consulted to determine the necessary clearances to any combustible rear wall or overlyin...

Page 4: ...d be accessible to operator from front or side 2 3 CONNECTION TO A GAS SUPPLY Gas supply piping and unit connection must be installed in accordance with regulations listed on front page of this document A gas isolating cock must be fitted to the supply in a position that is readily accessible to operator 2 4 CONNECTION TO AN ELECTRICAL SUPPLY Not applicable to these units 2 5 CONNECTION TO A WATER...

Page 5: ...njector 3 3 2 Removal of Pilot Cross Lighting Injectors Isolate main gas supply Undo pilot cross lighter supply pipe compression nut and remove pipe from pilot cross lighter burner Withdraw injector Replace in reverse order 3 4 FLAME FAILURE THERMOCOUPLE Undo nuts at pilot assembly and valve body Disconnect thermocouple interrupter from terminal block 2 7 INSTRUCTION TO USER After installing and c...

Page 6: ...ostat phial Disconnect thermostat electrical connections prior to removing thermostat Replace in reverse order 3 6 2 Recalibration of User Thermostat Remove knob from thermostat spindle taking care not to rotate it in either direction as this would change setting Steady spindle and rotate calibration screw clockwise to decrease and anti clockwise to increase the temperature 3 6 3 Checking the User...

Page 7: ...SECTION 4 SPARES When ordering spare parts always quote unit type and serial number This information will be found on data badge attached to base plate ...

Page 8: ......

Reviews: