background image

3

Installation (continued)

Figure 8.   

Optional Mounting Kit 19254-1.  

(Sold Separately)

Figure 9.  

Electrical Connections.

Make  connections  to  the  Terminal  Block,  Conduit 

Connector or the DIN Connector as shown below in 

Figure 9. “Electrical Connections”.

Pneumatic Connections

Clean all pipelines to remove dirt and scale before installation. 

Apply a minimum amount of pipe compound to the male threads of 

the fitting only.   

Do Not use teflon tape as a sealant.

  Start with 

the third thread back and work away from the end of the fitting to 

avoid the possibility of contaminating the transducer.  Install the 

transducer in the air line.

The inlet and outlet ports, in the lower valve body, are labeled on 

the ends of the transducer.  Tighten connections securely.  Avoid 

undersized fittings that will limit the flow through the transducer and 

cause a pressure drop downstream.    For more information, see 

Figure 2. “Outline Drawing” on page 2.

NOTE:

Instrument  quality  air,  per  ISA  Standards  S7.3-

1981, is required.  Use a filter to remove dirt and 

liquid in the air line ahead of the transducer for 

correct performance.  If an air line lubricator is 

used,  it  MUST  be  located  downstream,  beyond 

the transducer.

The  user  is  responsible  for  insuring  that  the 

environment in which the unit  will be installed, 

and  the  operating  gas,  are  compatible  with  the 

materials in the transducer. 

Electric Connections

Summary of Contents for T7800 Series

Page 1: ...0 30 psig SCFH 0 60 psig SCFH 0 120 psig SCFH Air Con sumption Set Point 0 psig 0 BAR 0 kPa 15 psig 1 0 BAR 100 kPa 30 psig 2 0 BAR 200 kPa 60 psig 4 0 BAR 400 kPa 120 psig 8 0 BAR 800 kPa Minimum Spa...

Page 2: ...5 15 64 133 0 5 15 64 133 0 4 57 64 124 3 4 57 64 124 3 _ V V S _ V V S 90 Alternating Positions 1 4 NPT Outlet Port 2 typical 1 4 NPT Inlet Port 2 typical 1 4 NPT Outlet Port 2 typical 1 4 NPT Inlet...

Page 3: ...nstall the transducer in the air line The inlet and outlet ports in the lower valve body are labeled on the ends of the transducer Tighten connections securely Avoid undersized fittings that will limi...

Page 4: ...le of a digital readout up to 150 psig with an accuracy of 1 Digital Volt Meter capable of a readout up to 30 mAwith an accuracy of 02 The following adjustments are provided Full Range Operation Lo Hi...

Page 5: ...Operation 0 30 0 2 0 200 HI 0 60 0 4 0 400 HI 0 120 0 8 0 800 HI Input Output psig BAR kPa 4 20 mA 0 5 1 5 0 10 1 9 VDC Span Position Table 3 Full Range Operation J1 Jumper J1 J1 J1 J1 A A A A B B B...

Page 6: ...cer Ring Diaphragm Assembly Foam Block Valve Body Assembly Screw Pintle Spring PIntle O Ring Plug Screw Diaphragm Spacer Ring Diaphragm Assembly Diaphragm Assembly Spring Foam Block Valve Body Assembl...

Page 7: ...ups CD T4 ED 18970 Entity I O AEx ia IIB T4 40 C to 80 C Non Incendive Class I II III Div 2 Groups ABCD T6 ED 18970 NIFW 40 C to 80 C Entity Parameters Vmax1 28VDC Ci4 12nF Imax2 100mA Li5 0mH Pmax3 0...

Page 8: ...be furnished with each product sold incorporating Fairchild s unit as a component thereof LEGAL NOTICE 1 Under certain extreme circumstances the non metallic parts incorporated in the enclosure of eq...

Page 9: ...derung bei 10 psig Versorgungs nderung Temperatureffekt 0 5 0 06 F Temperatur nderung typisch zur Spannweite Frequenzverlauf psig BAR kPa psig BAR kPa psig BAR kPa 0 30 0 2 0 0 200 0 60 0 4 0 0 400 0...

Page 10: ...pical Abbildung 4 TT7800 u ere Abmessungen OUT OUT IN IN OUT OUT IN IN OUT OUT IN IN Z S Z S Vent 1 11 16 42 9 1 5 16 33 3 27 32 21 5 27 32 21 5 2 1 4 57 1 2 1 4 57 1 1 33 64 38 7 1 33 64 38 7 4 21 32...

Page 11: ...2 HINWEIS Luft mit Ger tequalit t gem ISA Norm S7 31981 erforderlich Verwenden Sie zum ordnungsgem en BetriebvordemWandlereinenFilter derVerunreinigungen und Fl ssigkeiten in der Luftleitung entfernt...

Page 12: ...stellen der niedrigen hohen Spannweite 1 Bei einem Ausgangsbereich von 0 15 psig 15 30 psig 0 30 psig 30 60 psig 0 60 psig oder 60 120 psig muss der Schalter f r niedrige hohe Spannweite auf Niedrig g...

Page 13: ...FORWARD ACTING OPERATION Voltage Unit REVERSE ACTING OPERATION Current Unit REVERSE ACTING OPERATION Voltage Unit J7 Jumper Zero Adjustment Span Adjustment DAMPING ADJUSTMENT Decrease Damping Function...

Page 14: ...6 4 7 8 1 9 1 10 11 1 12 1 13 14 15 16 17 1 18 19 20 1 21 22 2 22 5 23 24 1 25 26 27 28 29 1 30 31 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 2 1 1 1 1 1 1 1 3 1 1 1 1 2 Abdeckung Verarbeitung Schraube...

Page 15: ...t KLASSIFIZIERUNG F R GEFAHRENBEREICHE FORTSETZUNG AUF DER N CHSTEN SEITE 1 Schlie enSiedasVentil dasdenWandlermitLuftversorgt Der Wandler muss nicht von der Luftzufuhrleitung getrennt werden 2 Entfer...

Page 16: ...erdem darf die Vorrichtung nur mit einem feuchten Tuch gereinigt werden Das ist besonders dann wichtig wenn die Vorrichtung an einem Standort der Zone 0 Einteilung 1 installiert ist 2 Das Geh use der...

Page 17: ...Norme europee EN61326 Pressione di effetto di alimentazione Cambio di 0 1 psig per un cambio di alimentazione di 10 psig Effetto sulla temperature 0 5 0 06 cambio di temperatura F dello span tipico Ri...

Page 18: ...l Figura 4 TT7800 Dimensioni esterne OUT OUT IN IN OUT OUT IN IN OUT OUT IN IN Z S Z S Vent 1 11 16 42 9 1 5 16 33 3 27 32 21 5 27 32 21 5 2 1 4 57 1 2 1 4 57 1 1 33 64 38 7 1 33 64 38 7 4 21 32 118 1...

Page 19: ...na 2 NOTA necessaria aria di qualit strumentale in accordo alle norme ISA S7 3 1981 Usare un filtro a monte del trasduttore per rimuovere sporco e liquidi presenti nella lineadell ariaeottenerecos una...

Page 20: ...Span Lo Hi basso alto 1 Impostare il commutatore dello span Lo Hi basso alto in posizione Lo basso per un intervallo di uscita 0 15 psig 15 30 psig 0 30 psig 30 60 psig 0 60 psig o 60 120 psig Per ul...

Page 21: ...TING OPERATION Current Unit REVERSE ACTING OPERATION Voltage Unit J7 Jumper Zero Adjustment Span Adjustment DAMPING ADJUSTMENT Decrease Damping Function Increase Damping Function LO SPAN SETTING Curre...

Page 22: ...2 6 3 6 4 7 8 1 9 1 10 11 1 12 1 13 14 15 16 17 1 18 19 20 1 21 22 2 22 5 23 24 1 25 26 27 28 29 1 30 31 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 2 1 1 1 1 1 1 1 3 1 1 1 1 2 Coperchio lavorazione mecc...

Page 23: ...a 4 Li Induttanza CLASSIFICAZIONE AREA PERICOLOSA SEGUE SULLA PAGINA SUCCESSIVA 1 Spegnerelavalvolachealimental ariaversoiltrasduttore Non necessario rimuovere il trasduttore dalla linea dell aria 2 T...

Page 24: ...o deve essere pulito solo con un panno umido Questo particolarmente importante se l apparecchio installato in una Zona 0 Divisione 1 2 L alloggiamento dell apparecchio serie TD_I7800 contiene material...

Page 25: ...d alimentation Changement de 0 1 psig pour un changement d alimentation de 10 psig Effet de la temp rature changement de temp rature de 0 5 0 06 F de l tendue standard R ponse en fr quence psig BAR kP...

Page 26: ...IN IN OUT OUT IN IN Z S Z S Vent 1 11 16 42 9 1 5 16 33 3 27 32 21 5 27 32 21 5 2 1 4 57 1 2 1 4 57 1 1 33 64 38 7 1 33 64 38 7 4 21 32 118 1 1 27 64 36 2 5 15 64 133 0 5 15 64 133 0 4 57 64 124 3 4...

Page 27: ...figura 2 Dimensiones generales en la p gina 2 NOTE Norme de qualit de l air des instruments ISA S7 3 1981 requise Utilisez un filtre pour retirer les salet s et liquides contenus dans le conduit d ai...

Page 28: ...tendue minimale maximale 1 Placez le dispositif de r glage de l tendue en position minimale Lo pouruneplagedesortiede0 15psig 15 30 psig 0 30psig 30 60psig 0 60psigou60 120psig Pour plus d informatio...

Page 29: ...Unit REVERSE ACTING OPERATION Voltage Unit J7 Jumper Zero Adjustment Span Adjustment DAMPING ADJUSTMENT Decrease Damping Function Increase Damping Function LO SPAN SETTING Current Voltage HI SPAN SET...

Page 30: ...10 11 1 12 1 13 14 15 16 17 1 18 19 20 1 21 22 2 22 5 23 24 1 25 26 27 28 29 1 30 31 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 2 1 1 1 1 1 1 1 3 1 1 1 1 2 Couverture Usinage Vis Vis Joint d tanch it Ass...

Page 31: ...maximale 3 Ci Capacitance 2 Imax Courant maximal 4 Li Inductance SUITE DE LA CLASSIFICATION DE ZONES DANGEREUSES LA PAGE SUIVANTE 1 Fermez la vanne qui alimente le transmetteur en air Il n est pas n c...

Page 32: ...ieu de type Zone 0 Division 1 De plus l quipement doit tre uniquement nettoy avec un chiffon humide Ceci est particuli rement important si l quipement est install dans un lieu de type Zone 0 Division...

Page 33: ...EN 61000 4 3 1998 A1 la Directiva 2014 30 EU sobre CEM y la norma europea EN 61326 Efecto de la presi n de suministro Cambio de 0 1 psig por cada 10 psig de variaci n de la presi n de suministro Efect...

Page 34: ...ra 4 TT7800 Dimensiones generales OUT OUT IN IN OUT OUT IN IN OUT OUT IN IN Z S Z S Vent 1 11 16 42 9 1 5 16 33 3 27 32 21 5 27 32 21 5 2 1 4 57 1 2 1 4 57 1 1 33 64 38 7 1 33 64 38 7 4 21 32 118 1 1...

Page 35: ...los requisitos de la norma ISA S7 3 1981 Coloque un filtro antesdeltransductorparaeliminarlasuciedadyell quido que puedan existir en la tuber a de aire y garantizar su correcto funcionamiento Si util...

Page 36: ...e el puente de amplitud baja alta en la posici n de amplitudaltaparaelrangodesalidade0 30 0 60o0 120 psig Para obtener m s informaci n consulte la tabla 3 Funcionamiento con rango completo en la p gin...

Page 37: ...it REVERSE ACTING OPERATION Voltage Unit J7 Jumper Zero Adjustment Span Adjustment DAMPING ADJUSTMENT Decrease Damping Function Increase Damping Function LO SPAN SETTING Current Voltage HI SPAN SETTIN...

Page 38: ...7 8 1 9 1 10 11 1 12 1 13 14 15 16 17 1 18 19 20 1 21 22 2 22 5 23 24 1 25 26 27 28 29 1 30 31 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1 2 1 1 1 1 1 1 1 3 1 1 1 1 2 Cubierta Mecanizado Tornillo Tornill...

Page 39: ...IGUIENTE 1 Cierre la v lvula de suministro de aire al transductor No es necesario desmontar el transductor de la tuber a de aire 2 Desmonte el conjunto del orificio 6 de la unidad Para obtenerm sinfor...

Page 40: ...si el equipo est instalado en un rea clasificada como zona 0 divisi n 1 Asimismo para la limpieza del equipo solo debe utilizarse un pa o h medo Esto es especialmente importante si el equipo est inst...

Reviews: