In case of failure of the panel:
- Make sure that the power supply to the electronic programmer

is 400V 

±

10%

- Make sure that the power supply to the Electric Motor

is 400V 

±

10%

- Check fuses
- Check photocells if contacts are normally closed
- Check all NC contacts
- Check that no voltage drop has occurred from the control
  panel to the electric motor

Led Status Indication:

L1= 230V 50Hz power supply. Alight
L2= Photocells, if obstructed light goes off
L3= Open. Alight whenever an Open pulse is given
L4= Close. Alight whenever a Close pulse is given
L5= Stop. It goes off on pulsing Stop
L6= Radio. It goes on by pressing a transmitter button
L7= Gate Status; it flashes on gate opening
L8= Limit switch Close; off when gate is closed
L9= Limit switch Open; off when gate is open
L10= It stays on for a time equal to the time set on T4

The electronic control panel Elpro 10 Plus, new generation, is designed to operate the sliding gates. Power supply is 230/400V three-phase. Built in full compliance with
BT 93/68/CE Low/High Voltage and EMC 93/68/CE Electro-Magnetic Compatibility Regulations. Fitting operations are recommended by a qualified technician in conformity
to the existing safety standards.
The manufacturing company declines any responsability for incorrect handling and application; also, it reserves the right to change or update the control panel any time.

PLEASE NOTE:
- The control panel must be installed in a sheltered, dry place, inside the box provided with it.
- Make sure that the power supply to the electronic programmer is 400V 

±

10%

- Make sure that the power supply to the Electric Motor is 400V 

±

10%

- For distances of over 50 metres we recommend using  electric cables with bigger sections.
- Fit the mains to the control panel with a 0.03A high performance circuit breaker.
- Use 1.5mm

2

 section wires for voltage supply, electric motor and flashing lamp.

  Maximum recommended distance 50m.
  Use 1mm

2

 section wires for limit switches, photocells, push-buttons/key-switch and accessories.

- Bridge terminals 1 and 2 if no photocells are required.
- Bridge terminals 3 and 6 if no key- or push-button switches are required.
N.W: To fit extra accessories such as lights, CCTV etc. use only solid state relays to prevent damages to the microprocessor.

DIP-SWITCH

1

4 5 6 7 8

2

ON

OFF

3

Dip-Switch:

1= ON. Photocells. Stop while opening
2= ON. Radio. No reversing while opening
3= ON. Automatic closing
4= ON. Preflashing activated
5= ON. Radio. Step by step. Stop in between
6= ON. Dead Man Control (Dip 4=OFF and Dip 3=OFF)
7= ON. No lamp on during dwell time
8= OFF. No function

1

2

Button switch:

3

4

5

6

Photocells and Safety Edge:

12 13

PHOTOCELLS AND
SAFETY EDGE

24V (500 mA) OUTPUT
(MAX. LOAD:
2 PAIRS PHOTOCELLS
1 RADIO RECEIVER)

Push Button Switch Pulin3:

26

27

28

3

COMMON

Led to indicate status
of Open - Stop - Close
switches

RS RS

Connect a 12VAC
Relay (T4 Trimmer
Time from 2s to 255s)
to operate a 230V lamp

Electric lock:

RS RS

Set the T4 Trimmer Time
to the lowest value The
electric lock is excited
for 2 seconds

7

3

LOW VOLTAGE ELECTRICAL CONNECTIONS

1

DIP-SWITCH 1:

ON: Photocells stop gate while opening,
       reverse it on closing once obstacle is
       removed

OFF: Photocells do not stop gate while
        opening, reverse it on closing in
        case of an obstacle

STOP

COMMON

OPEN

CLOSE

Limit switch:

10

COMMON

8

9

LIMIT SWITCH

CLOSE

LIMIT SWITCH

OPEN

Radio Contact:

COMMON

RADIO

CONTACT

- Open/Close (Standard)
- Travel reversing on
  pulsing
- Step by step

2

5

ON: Step by step. Stop in between

OFF: Standard operating mode

ON: Gate is not reversed while opening

OFF: Any pulse reverses the gate

DIP-SWITCH 2 and 5 (NEVER set BOTH of
them to ON at the same time):

Light 

ON

 = Open gate

Light 

OFF

 = Closed gate

Flashing 

(fast) 0.5s

 = Closing gate

Flashing 

(normally) 1s

= Opening gate

Flashing 

(slowly) 2s

= gate is stopped

24V 3W Indication Light:

3

11

Courtesy light:

Flashing lamp:

19 20

 230V MAX 25W

4

Power supply:

Three-phase
Motors (400V):

ELECTRIC POWER CONNECTIONS

-

+

T1

MOTOR RUN TIME

OPEN / CLOSE

from 5 to 128s

T2

-

+

DWELL TIME

from 5 to 128s

7

230V

400V

CAPACITOR

18

16

17

COMMON

M

MOTOR

U

W

V

DIP-SWITCH 4 and 7:

ON: Pre-flashing

OFF: No pre-flashing

ON: Lamp is not operating during
       Dwell Time. Automatic Mode.

OFF: It flashes during Dwell Time .
         Automatic Mode.

21

22

T

R

S

LIVE

23

22

400V 

±

10% 50Hz

THREE-PHASE

LIVE

LIVE

PLUS

10

DRWG. NO. 

4135

PIC. 12

Summary of Contents for FIBO 300

Page 1: ...G B INSTALLATION MANUAL...

Page 2: ...ion for intense opening closing cycles The drive shaft is in direct contact with a mechanical torque control device worm and gear are made of bronze and steel and are supported by bearings in an oil b...

Page 3: ...THE PLUGS ONCE THE PLUG PROTRUSION HAS BEEN ESTABLISHED TIGHTEN THE NUT TO THE FLOOR IN ORDER TO FIRMLY FIX THE PLUG IN THE HOLE THEN UNSCREW AND REMOVE THE NUT INSERT THE PLUGS IN THE HOLES LEAVING A...

Page 4: ...te Pic 6 Temporarily clamp the rack to the gate levelling it using a spirit level for the entire length of the gate the rack must mesh the idle Fibo 300 driving gear I smoothly and without friction Th...

Page 5: ...located on the front beneath the electric power panel E P P tighten in order to increase the torque and loosen in order to reduce the torque Pic 10 PIC 8 PIC 9 RACK SPARE RACK AS A PITCH GAGE IMPORTA...

Page 6: ...ING ON AUTOMATIC CLOSING ON PREFLASHING ACTIVATED ON RADIO STEP BY STEP STOP IN BETWEEN ON DEAD MAN CONTROL Dip 4 OFF and Dip 3 OFF ON NO LAMP ON DURING DWELL TIME OFF NO FUNCTION EXT TIME PEDESTRIAN...

Page 7: ...21 A 1 2 4 6 22 A 2 1 2 3 4 5 M 16 17 18 19 20 21 22 23 R S T THREE PHASE ELECTRIC MOTOR 230 V 25 W max FLASHING LAMP SUPPLY VOLTAGE 230 400 V 10 THREE PHASE HIGH VOLTAGE 10 A 380 V FUSES POWER CONTAC...

Page 8: ...d Bridge terminals 3 and 6 if no key or push button switches are required N W To fit extra accessories such as lights CCTV etc use only solid state relays to prevent damages to the microprocessor DIP...

Page 9: ...13 13 17 10 15 16 14 PIC 12 Holdonswitched Deadman control Pedestrian Opening Trimmer T3 OPERATING MODES from 3 to 30s It can be activated by any pulse eg by remote control superior to 2s 3 DIP SWITCH...

Page 10: ...provided Pic 11 and Pic 15 following the Elpro 10 PLUS function logic description Drwg 3499 p 6 E P P ELECTRIC POWER PANEL WITH THE ELPRO 10 PLUS PROGRAMMER INCORPORATED SUPPORT PREPARED FOR ATTACHING...

Page 11: ...cles a year 8 hours a day 131 000 FIBO 300 GEAR MOTOR Output revolutions 40 7 rpm Drive gear Z 24 Module 4 0 Ratio 1 32 Maximum nominal torque 128 Nm Transfer speed 12 m min Hydraulic oil type AGIP RO...

Page 12: ...isconnect the mains switch before opening the electrical wire junction box cover The whole automation should be earthed with the yellow green wire We recommend reading the Safety Norms suggestions and...

Reviews: