AUTOMATIC / SEMI-AUTOMATIC:

Automatic cycle:

 by one pulse from the open command the gate opens and stops in

dwell mode for the time as pre-set on the

 dwell trimmer

. When this time expires the gate 

closes automatically.

Semi-automatic cycle: 

by one pulse from the open command the gate opens and

stops in fully open position. To close the gate, a close pulse is needed.

Dip-switch setting and LED indication of functions

Dwell trimmer: 

adjust dwell time

on automatic mode from 
1s up to 220s

3

ON

: Automatic closing

OFF

: Semi-automatic, closing by pulse

DIP-SWITCH-A N°3:

Description

DIP-SWITCH-A N°8:

PEDESTRIAN OPENING:

With the gate in fully closed position, a pulse to terminals
P-P operates the gate for pedestrians.

(On pedestrian mode, it is advisable to set Dip-A N°3= ON
for automatic re-closing).

The function 

"pedestrian opening"

 is not in service during

the first operation cycle, after a power failure.

9

ON: 

DSA safety control enabled

OFF: 

DSA safety control disabled

DIP-SWITCH-A N°9:

DEADMAN (HOLD-ON-SWITCHED) CONTROL:

The open/close operations are achieved by " holding on a command
switched" (the relays are not self-holding) and consequently the user must
be actively present during  gate movements until the push-button or the
key-switch is released.

6

ON: 

Deadman control enabled

OFF: 

Deadman control disabled

DIP-SWITCH-A N°6:

3

DIP-SWITCH-A N°3:

3 4

24V ac output

for photocell TX

enabled for 

DSA control

38 39

FUNCTIONS FOR SLIDING GATE OPENING

PARTY FUNCTION

OPEN-AND-HOLD BY EXTERNAL CLOCK:

Connect the clock NO contact to OPEN terminals
No. 4 and COMMON No. 3, and activate automatic 
closing by setting Dip-Switch No. 3=ON.

How it works:  program the opening time on the clock. 
At the preset time, the gates will open and remain 
open (the flashing light will turn off) and will not accept 
any  other  command  (not  even  radio  commands) 
until the time set on the clock expires.
When this time expires the gates close automatically 
after the pause time.
While the gates are held open by the time set on the 
"clock",  the  indication  light  keeps  giving  out  two 
consecutive flashes followed by a long pause.

-

+

DSA: PHOTOCELL AUTOMATIC CONTROL:

For  the 

DSA  

control  (

D

evice  for 

S

afety 

A

uto-test)  it  is  necessary  to 

connect  

only  the  photocell  transmitters  (TX)

  to  this  output  and 

select 

Dip-A No.9=ON

: if this function is enabled, ELPRO 37 checks 

that all the connected photocell devices are cleared from obstacles 
and properly working before starting any door/gate movements, 
otherwise the door/gate is not started.

RE-CLOSING BY PASSING ACROSS THE PHOTOCELLS: in opening and dwell cycles
(DIP-A N°3=ON)

Gate is automatically closed after 3s from passing between the photocells.

L0 OFF = 

no pedestrian contact given,

                it goes on by pulsing for pedestrians

1 2 3 4 5 6

OPEN
PEDESTRIANS

8

ON

: Automatic closing on passing across

       the photocells after 3 seconds

OFF: 

No automatic closing on passing    

        across the photocells 

COMMON

NO

External Clock

ON: 

Automatic closing

OPEN

COMMON

IMPORTANT: use always and only with
Dip-A N°3= ON

-

+

PEDESTRIAN

OPENING

1s - 45s

meccanica

FADINI

37

SINGLE – THREE PHASE ELECTRONIC CONTROL BOARD WITH ELECTRONIC BRAKE 
FOR SLIDING GATE AUTOMATIC SYSTEMS WITH OR WITHOUT LIMIT SWITCHES

GB

Summary of Contents for Elpro 37

Page 1: ...T TIME ELECTRIC LOCK OUTPUT Elektronische Steuerung einphasig dreiphasig mit Elektrobremse f r Schiebetore und Automationen mit oder ohne Endschalter max 1 5 PS dreiphasig oder 1 0 PS einphasig ELEKTR...

Page 2: ...ty edge or photocell protecting opening not obstructed ATTENTION Before starting the electrical connections check the voltage 230V or 400V selector switch to be set correctly In cases a motor with mec...

Page 3: ...on by any radio pulse Dip Switch A 1 ON Photocells stop gate in opening 2 ON Radio no reversing in opening 3 ON Automatic closing 4 ON Pre flashing enabled 5 ON Radio step by step 6 ON Dead man 7 ON F...

Page 4: ...goes off Safety edge in opening In series if safety edges are mechanical N C 32 33 Selecting functioning JB JB 1 2 Gate travel is reversed on Opening and Closing for a short spell 1 2 Gate travel is...

Page 5: ...0 HP or three phase 400V max 1100W 1 5 HP 24V Output FA DIN I Astro 43 FA D I N I 24Vac OUTPUT max load No 3 pairs photocells No 1 radio receiver No 1LED Chis 37 Chis E 37 key switch Instructions are...

Page 6: ...ed Yellow Green Fuse 1A Common 63 64 65 66 60 61 Optional Traffic lights plug in card for 230V Lamps Item 7282L Dip switch A 4 ON Pre flashing enabled traffic lights red yellow green 4 OFF Pre flashin...

Page 7: ...L CLOCK Connect the clock NO contact to OPEN terminals No 4 and COMMON No 3 and activate automatic closing by setting Dip Switch No 3 ON How it works program the opening time on the clock At the prese...

Page 8: ...brake function set the Dip switch A No 12 in ON and adjust the electronic brake intensity by the selector in the figure The factory preset adjustments are suitable for most installations For a more p...

Page 9: ...10 2016...

Reviews: