Dear user 

1

Congratulations on purchasing your Faber product, 
a quality product that will provide you with the 
warmth and atmosphere for many years. Please 
read the user manual before using the fire. Should, 
despite the careful final checks, a malfunction 
occur, please contact your Faber dealer. 

 

 

Please note:

  

The data of your fire is available in the user 
manual. 

 

Introduction 

1.1

Only have the appliance installed by a qualified 
installer according to the gas safety regulations. 
Read this installation manual properly. 

 

Please check 

1.2

Check the fire for transport damage and report any 
damage immediately to your dealer.  

 

Check that the following parts are included: 
 

1.

 

Decoration material  

2.

 

Cover Ionisation plug .(fig.3.1 a) 

3.

 

Suction Cups  

4.

 

warranty card  

5.

 

User’s manual  

6.

 

Installation manual  

7.

 

Instruction card  for decoration material 

8.

 

Remote controller 

9.

 

ranges of restrictors (fig.4.2) 

10.

 

Set long legs (fig.1.2 c ) 

11.

 

Decorative solid cover trims (method 1 
and 2) and integrated cover trim Q 
(Method 3) (fig. 2.1a tm 2.1 c) 

12.

 

magnet snapper (fig.2.1R) 

 

CE Declaration 

1.3

Glen Dimplex Benelux certifies that this Faber fire 
complies with the essential requirements of the 
gas appliances directive. 
Product: gas room heater 
Model: Triple Premium XXL 
Applicable EC directives: 90/396/EEC 
Harmonised standards applied: NEN-EN-613 
NEN-EN-613/A1 
 
This Declaration is invalid, if without the written 
permission of Glen Dimplex Benelux: 

 

Changes are made to the appliance. 

 

The fire is connected to other exhaust 
materials than specified. 

 

Safety instructions 

2

 

The unit must be installed and subsequently 
serviced every year and maintained in 
accordance with these instructions and the 
applicable national and local regulations. 

 

Ensure that the data on the type label matches 
the local gas type and pressure. 

 

The settings and the construction of the fire 
must not be changed! 

 

The 230V electric cable may be only replaced 
by a qualified person. 

 

Ensure that the log layout (if applicable) 
exactly matches the relevant photographs in 
the instruction leaflet and never add extra 
decorative material that was not supplied with 
the fire.   

 

The pilot flame must never be obstructed and 
particular care must be taken when placing 
the logs, pebbles or stones which are supplied 
with the fire. 

 

The unit is for atmosphere and heating 
purposes. This means that all surfaces, 
including the glass, can be very hot (over 
100°C); exceptions to this are the bottom of 
the fire and the control elements. 

 

Do not place any combustible materials within 
0.5m of the radiation area of the fire.  

 

Before use, remove all stickers, protective film 
and any protective rubber strips from the 
glass. 

 

Ensure adequate ventilation of the room when 
using the fire for the first time. Run the fire at 
the highest setting for several hours so that 
the paint will have the chance to harden and 
any possible vapours can be released safely. 
Keep children and pets out of the room during 
this process. 

 

Please note  

Through the natural air circulation of the fire 
moisture and uncured volatile components 
from paint, building materials and carpeted 
floors, etc. are attracted. These parts can 
settle as soot on cold surfaces. Therefore do 
not light the fire shortly after installation

 
 
 
 
 
 
 
 

Summary of Contents for Triple Premium XXL

Page 1: ...Triple Premium XXL 40011590 1529 Triple Premium XXL ENG ...

Page 2: ...Installatie handleiding 2 1 1 1 2 1 3 1 4 1 5 1 6 C ...

Page 3: ...Installatie handleiding 3 1 7 1 8 1 9 2 1 a 2 1 b 2 1 c 2 1 d C ...

Page 4: ...Installatie handleiding 4 2 2 2 3 2 4 2 5 2 7 2 8 2 9 H F F X C X T S A ...

Page 5: ...Installatie handleiding 5 3 1 3 1 a 3 1 b 3 1 c ...

Page 6: ...Installatie handleiding 6 4 1 4 2 5 1 a 5 1 b 5 1 c 5 1 d 5 1 e ...

Page 7: ...t materials than specified Safety instructions 2 The unit must be installed and subsequently serviced every year and maintained in accordance with these instructions and the applicable national and local regulations Ensure that the data on the type label matches the local gas type and pressure The settings and the construction of the fire must not be changed The 230V electric cable may be only rep...

Page 8: ...s connection pipe with at least meter extra length to allow for installation and service of the control unit fig 1 7 False chimney breast or other 3 4 structure The False chimney should be made entirely of non combustible material The space above the fire should always be ventilated using grids with minimal free passage of 200cm per grid Never build directly onto the built in frame of the applianc...

Page 9: ...nection on the gas valve Positioning of the fire 4 3 Take the installation requirements into account see Chapter 3 Place the unit in the desired position and set the height and level of the fire with the adjustable legs supplied Fig 1 2c Rough height adjustment can be achieved with the extendable leg or with the long legs supplied Fine adjustment can be achieved with the adjustable feet Suspended ...

Page 10: ...S T and Q covers fig 2 7 to 2 9 C spacer fig 2 2 B and C F fig 2 3 D fig 2 2 H fig 2 5 Please note Ensure that the fire is not load bearing with regard to the false chimney breast or other structural elements Pay special attention to the following points 1 Check during work that the glass can be inserted and removed easily 2 Check during work that the covers T fig 2 7 and 2 8 or Q fig 2 9 fit corr...

Page 11: ... the chips on the burner and on the cover plate Prevent a thick layer on the burner this adversely affects the flame pattern Glow wire 6 1 1 The glow wire gives a decorative glow effect Pull the wire well apart and place tufts in different places on the burner Please note Do not use the glow wire near the ignition and ionisation plugs as this can cause a short circuit in the ignition system Pebble...

Page 12: ...and connect a pressure gauge hose to the test point Connect your meter on the measure point B see fig 1 7 Open the gas tap isolator The pressure must match the value specified in the technical data of this manual When the inlet pressure is 5mb higher or lower do not connect the appliance and get in contact with the gas supply company How to check burner pressure This test can only be performed if ...

Page 13: ... with your fire is to use the free Faber Flue App which can be download from INTERNET BlackBerry Android PC with Google Chrome browser APP store iPhone iPad and Mac Google Play Android smartphones and Android tablets Alternatively use the flue calculation table see tables below and sections 12 and 13 The alternatives of outlet lengths and any restrictors are set out in the restrictor table In the ...

Page 14: ...x 30 or 45 bends in the vertical part Table Select from the table the correct vertical TVH and horizontal length THL If the result is x or if the values are outside the table then the combination is not allowed The TVH or THL can be adjusted to achieve a viable system If a value is indicated check that the calculated STL value is not lower than indicated in the table In this case STL must be adjus...

Page 15: ...x x x x x x x x x x 9 0 2 x x x x x x x x x x 10 0 2 x x x x x x x x x x 11 30 2 x x x x x x x x x x 12 30 2 x x x x x x x x x x 13 30 2 x x x x x x x x x x 14 30 2 x x x x x x x x x x 15 30 2 x x x x x x x x x x 16 40 2 x x x x x x x x x x 17 40 2 x x x x x x x x x x 18 40 2 x x x x x x x x x x 19 40 2 x x x x x x x x x x 20 40 2 x x x x x x x x x x 21 50 2 x x x x x x x x x x 22 50 2 x x x x x x...

Page 16: ...0 4 60 4 60 4 50 4 50 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 50 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 80 4 80 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 80 4 80 4 80 4 70 4 70 4 70 4 60 4 x x x x 15 80 4 80 4 80 4 80 4 70 4 70 4 70 4 x x x x 16 80 4 80 4 80 4 80 4 80 4 70 4 70 4 x x x x 17 80 4 80 4 80 4 80 4 80 4 80 4 70 4 x x x x 18 80 4 80 4 80 4 80 4 80 4 80 4 80 4 x x x x ...

Page 17: ...Installatie handleiding 17 Example 12 fig 12 1 fig 1 2 2 fig 12 3 ...

Page 18: ...k component that is placed on the fire value completed Flue length from 0 1 0 45 m 0 2 Flue length from 0 5 0 90 m 0 5 Flue length from 1 0 1 40 m 1 Flue length from 1 5 2 00 m 1 5 Flue length from 2 00 m und mehr 2 Bends 90 0 1 Bends 45 oder 30 0 2 Roof terminal 1 Wall terminal 0 Total ...

Page 19: ...e horizontal flue length x 1 5 45 bends in the horizontal flue length x 1 90 bends from Vertical to horizontal Vice versa x 0 4 45 bends from Vertical to horizontal Vice versa x 0 2 Pipes running upwards at an angle In meters x 0 7 total _______ Meter Search in the table at TVH and THL and enter the value that is found Found value If the detected value is a number check whether the completed STL i...

Page 20: ...mm Ectra information found value behind the comma Mark which is applied Install the air reducer plate See the installation manual 0 1 Install the adapter 200 130 to 150 100mm direct on top of the fire 0 2 In case of wall terminal Install the adapter 200 130 to 150 100mm before the last bend In case of roof terminal Install the adapter 200 130 to 150 100mm before the terminal 0 3 In case of roof te...

Page 21: ... mbar 20 30 37 Gas rate at 15ºC and 1013 mbar M3h 1 511 0 461 0 588 Gas rate at 15ºC and 1013 mbar gr h 1180 1100 Burner pressure at full mark mbar 11 5 24 33 5 Burner pressure low mark mbar 4 6 6 Injector main burner mm 660 660 220 230 220 230 Diameter inlet outlet mm 200 130 200 130 200 130 Gas control valve SIT 845 SIT 845 Sit 845 Gas connection Electrical connection V 220 220 220 Batteries sen...

Page 22: ...UK indication Position Distance in mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each othe...

Page 23: ...Installatie handleiding 23 Drawings 16 Triple Premium XXL 16 1 ...

Page 24: ...Installatie handleiding 24 Builder s opening and control box dimensions 16 2 ...