background image

 

Installatie handleiding

 

 

23 < 

<

 

<

 

<

 

 

 Drawings  

16

 

Triple Premium XXL  

16.1

 
 
 

 

 

 

Summary of Contents for Triple Premium XXL

Page 1: ...Triple Premium XXL 40011590 1529 Triple Premium XXL ENG ...

Page 2: ...Installatie handleiding 2 1 1 1 2 1 3 1 4 1 5 1 6 C ...

Page 3: ...Installatie handleiding 3 1 7 1 8 1 9 2 1 a 2 1 b 2 1 c 2 1 d C ...

Page 4: ...Installatie handleiding 4 2 2 2 3 2 4 2 5 2 7 2 8 2 9 H F F X C X T S A ...

Page 5: ...Installatie handleiding 5 3 1 3 1 a 3 1 b 3 1 c ...

Page 6: ...Installatie handleiding 6 4 1 4 2 5 1 a 5 1 b 5 1 c 5 1 d 5 1 e ...

Page 7: ...t materials than specified Safety instructions 2 The unit must be installed and subsequently serviced every year and maintained in accordance with these instructions and the applicable national and local regulations Ensure that the data on the type label matches the local gas type and pressure The settings and the construction of the fire must not be changed The 230V electric cable may be only rep...

Page 8: ...s connection pipe with at least meter extra length to allow for installation and service of the control unit fig 1 7 False chimney breast or other 3 4 structure The False chimney should be made entirely of non combustible material The space above the fire should always be ventilated using grids with minimal free passage of 200cm per grid Never build directly onto the built in frame of the applianc...

Page 9: ...nection on the gas valve Positioning of the fire 4 3 Take the installation requirements into account see Chapter 3 Place the unit in the desired position and set the height and level of the fire with the adjustable legs supplied Fig 1 2c Rough height adjustment can be achieved with the extendable leg or with the long legs supplied Fine adjustment can be achieved with the adjustable feet Suspended ...

Page 10: ...S T and Q covers fig 2 7 to 2 9 C spacer fig 2 2 B and C F fig 2 3 D fig 2 2 H fig 2 5 Please note Ensure that the fire is not load bearing with regard to the false chimney breast or other structural elements Pay special attention to the following points 1 Check during work that the glass can be inserted and removed easily 2 Check during work that the covers T fig 2 7 and 2 8 or Q fig 2 9 fit corr...

Page 11: ... the chips on the burner and on the cover plate Prevent a thick layer on the burner this adversely affects the flame pattern Glow wire 6 1 1 The glow wire gives a decorative glow effect Pull the wire well apart and place tufts in different places on the burner Please note Do not use the glow wire near the ignition and ionisation plugs as this can cause a short circuit in the ignition system Pebble...

Page 12: ...and connect a pressure gauge hose to the test point Connect your meter on the measure point B see fig 1 7 Open the gas tap isolator The pressure must match the value specified in the technical data of this manual When the inlet pressure is 5mb higher or lower do not connect the appliance and get in contact with the gas supply company How to check burner pressure This test can only be performed if ...

Page 13: ... with your fire is to use the free Faber Flue App which can be download from INTERNET BlackBerry Android PC with Google Chrome browser APP store iPhone iPad and Mac Google Play Android smartphones and Android tablets Alternatively use the flue calculation table see tables below and sections 12 and 13 The alternatives of outlet lengths and any restrictors are set out in the restrictor table In the ...

Page 14: ...x 30 or 45 bends in the vertical part Table Select from the table the correct vertical TVH and horizontal length THL If the result is x or if the values are outside the table then the combination is not allowed The TVH or THL can be adjusted to achieve a viable system If a value is indicated check that the calculated STL value is not lower than indicated in the table In this case STL must be adjus...

Page 15: ...x x x x x x x x x x 9 0 2 x x x x x x x x x x 10 0 2 x x x x x x x x x x 11 30 2 x x x x x x x x x x 12 30 2 x x x x x x x x x x 13 30 2 x x x x x x x x x x 14 30 2 x x x x x x x x x x 15 30 2 x x x x x x x x x x 16 40 2 x x x x x x x x x x 17 40 2 x x x x x x x x x x 18 40 2 x x x x x x x x x x 19 40 2 x x x x x x x x x x 20 40 2 x x x x x x x x x x 21 50 2 x x x x x x x x x x 22 50 2 x x x x x x...

Page 16: ...0 4 60 4 60 4 50 4 50 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 50 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 80 4 80 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 80 4 80 4 80 4 70 4 70 4 70 4 60 4 x x x x 15 80 4 80 4 80 4 80 4 70 4 70 4 70 4 x x x x 16 80 4 80 4 80 4 80 4 80 4 70 4 70 4 x x x x 17 80 4 80 4 80 4 80 4 80 4 80 4 70 4 x x x x 18 80 4 80 4 80 4 80 4 80 4 80 4 80 4 x x x x ...

Page 17: ...Installatie handleiding 17 Example 12 fig 12 1 fig 1 2 2 fig 12 3 ...

Page 18: ...k component that is placed on the fire value completed Flue length from 0 1 0 45 m 0 2 Flue length from 0 5 0 90 m 0 5 Flue length from 1 0 1 40 m 1 Flue length from 1 5 2 00 m 1 5 Flue length from 2 00 m und mehr 2 Bends 90 0 1 Bends 45 oder 30 0 2 Roof terminal 1 Wall terminal 0 Total ...

Page 19: ...e horizontal flue length x 1 5 45 bends in the horizontal flue length x 1 90 bends from Vertical to horizontal Vice versa x 0 4 45 bends from Vertical to horizontal Vice versa x 0 2 Pipes running upwards at an angle In meters x 0 7 total _______ Meter Search in the table at TVH and THL and enter the value that is found Found value If the detected value is a number check whether the completed STL i...

Page 20: ...mm Ectra information found value behind the comma Mark which is applied Install the air reducer plate See the installation manual 0 1 Install the adapter 200 130 to 150 100mm direct on top of the fire 0 2 In case of wall terminal Install the adapter 200 130 to 150 100mm before the last bend In case of roof terminal Install the adapter 200 130 to 150 100mm before the terminal 0 3 In case of roof te...

Page 21: ... mbar 20 30 37 Gas rate at 15ºC and 1013 mbar M3h 1 511 0 461 0 588 Gas rate at 15ºC and 1013 mbar gr h 1180 1100 Burner pressure at full mark mbar 11 5 24 33 5 Burner pressure low mark mbar 4 6 6 Injector main burner mm 660 660 220 230 220 230 Diameter inlet outlet mm 200 130 200 130 200 130 Gas control valve SIT 845 SIT 845 Sit 845 Gas connection Electrical connection V 220 220 220 Batteries sen...

Page 22: ...UK indication Position Distance in mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each othe...

Page 23: ...Installatie handleiding 23 Drawings 16 Triple Premium XXL 16 1 ...

Page 24: ...Installatie handleiding 24 Builder s opening and control box dimensions 16 2 ...

Page 25: ...Installatie handleiding 25 Builder s opening and ventilation grills dimensions 16 3 ...

Page 26: ......

Reviews: