Installatie handleiding
20 <
<
<
<
Is the found value “X” then the flue run is not possible
Solution: change the TVH or THL
If the STL value is less than as specified in the top row of the table , the flue run is not possible .
Solution: starter length to low! see for the minimum length in the top row of the table
Result
Restrictor size = found value before the comma
mm
Ectra information = found value behind the comma
Mark which is applied
Install the air reducer plate! See the installation manual!
0,1
Install the adapter 200/130 to 150/100mm direct on top of the fire
0,2
In case of wall terminal:
Install the adapter 200/130 to 150/100mm before the last bend.
In case of roof terminal
:
Install the adapter 200/130 to 150/100mm before the terminal.
0,3
In case of roof terminal (Always size 100/150mm):
install the adapter 200/130 to 150/100mm just before the terminal.
In case wall terminal:
Use the 200/130mm wall terminal
0,4
Summary of Contents for Triple Premium XXL
Page 1: ...Triple Premium XXL 40011590 1529 Triple Premium XXL ENG ...
Page 2: ...Installatie handleiding 2 1 1 1 2 1 3 1 4 1 5 1 6 C ...
Page 3: ...Installatie handleiding 3 1 7 1 8 1 9 2 1 a 2 1 b 2 1 c 2 1 d C ...
Page 4: ...Installatie handleiding 4 2 2 2 3 2 4 2 5 2 7 2 8 2 9 H F F X C X T S A ...
Page 5: ...Installatie handleiding 5 3 1 3 1 a 3 1 b 3 1 c ...
Page 6: ...Installatie handleiding 6 4 1 4 2 5 1 a 5 1 b 5 1 c 5 1 d 5 1 e ...
Page 17: ...Installatie handleiding 17 Example 12 fig 12 1 fig 1 2 2 fig 12 3 ...
Page 23: ...Installatie handleiding 23 Drawings 16 Triple Premium XXL 16 1 ...
Page 24: ...Installatie handleiding 24 Builder s opening and control box dimensions 16 2 ...
Page 25: ...Installatie handleiding 25 Builder s opening and ventilation grills dimensions 16 3 ...
Page 26: ......