Calculation of flue system
The possibilities for the lengths of flue pipes and the possible restrictors have been recorded
in a table (see chapter 12 ) This table works with a vertical and a horizontal length.
To define the vertical length all lengths of flue pipes in a vertical direction should
be added up.
-
The roof terminal always counts as 1 metre.
To define the horizontal length all lengths of flue pipes in a horizontal direction
should be added up.
-
every 90° bend in the horizontal part counts as 2 metres.
-
every 45° bend in the horizontal part counts as 1 metre.
-
Turns from vertical to horizontal or vice versa are not reckoned in the
calculation.
-
The wall terminal always counts as 1 metre.
If there is transit under 45° then the real vertical and horizontal lengths should be
calculated.
11.1
Points of particular interest:
The maximum chimney length is 12 metres.
You can never start with a 90° or 45° bend from the appliance.
You should always start with 1 metre vertical if the horizontal transit is more than 1
metre.
You should never start with a cut-down pipe from the appliance.
Summary of Contents for Glance
Page 1: ...Glance 40010576 0951 Installation guide ENG ENG ...
Page 2: ...L 1 1 1 1 2 1 3 1 4 1 5 A ...
Page 3: ...L 2 2 1 2 2 2 3 2 4 B 1 2 A ...
Page 4: ...L 3 2 5 2 6 110mm 3 1 3 2 ...
Page 21: ...L 20 14 Dimension of the appliance ...
Page 22: ...L 21 15 Dimension of the appliance with frame ...
Page 23: ...L 22 16 Ventilation Grills ...
Page 24: ...L 23 17 Dimension Service Hatch ...
Page 25: ...24 L ...