TECHNICAL INFORMATION 

 

These self-excited and self-regulating generators, although overall dimensions  have been reduced to a minimum, 
are designed for high-level electrical performance and the maximum in operating reliability. 

 

PRELIMINARY CHECKS: 

Before touching the machines, perform a thorough and in depth visual 
inspection, checking that components are correctly connected  up and 
that no cables or terminals are broken or loose. 

 

 

STARTING UP:  

Make sure, when starting up, that cooling air intake and discharge openings 
are free and unblocked.  We also recommend (when the machine operates 
in a dusty environment) do periodic checks to make sure it is properly 
ventilated 

 

THE IMPORTANCE OF SPEED:  

Frequency and voltage depend directly on rotation speed. This must be 
kept as constantly as possible on its nominal value no matter what the 
load. Drive motor speed control systems generally have a small drop in 
speed between no load and loaded conditions. We therefore 
recommend setting no load speed 3÷4% above nominal speed. 

 

CHECKING VOLTAGE:  

All the machines are regulated during factory testing. If voltage 
readings differ from the value indicated on the name plate, this maybe 
caused by a mistaken reading or by a different rotation speed and we 
recommend regulating motor speed in order to have nominal RPM 
under loaded conditions. 

 

CHECKING THE DIODES:  

For the ohmmeter test it is best to disconnect the diode from its circuit. 
Measure continuity in one direction only. The test can also be made 
without disconnecting the diode form the circuit, using a 12V battery 
and a 45 watt light bulb (automobile light) as shown in the illustration. 
The light should turn totally on only in one direction, as shown below. 

Summary of Contents for BD - 400SV

Page 1: ...Power Instruction Manual for Model BD 400SV BELT DRIVEN 3600 RPM GENERATOR Manufacturing of Vehicle Mounted Generators Hydraulic Generators P O Box 582 Chester NY 10918 845 469 9151 Fax 845 469 7871 Web Site E mail www fabcopower com ...

Page 2: ...ATION MODEL BD 400SV GENERATOR BRUSHLESS GENERATOR 3600 60 Hz GENERATOR VOLTAGE 120 or 120 240 MOTOR STARTING 300 SURGE VOLTAGE REGULATOR INHERENT OUTPUT 3750 WATTS CONTINUOUS 4000 WATTS PEAK AT 100 F OIL TEMPERATURE MAXIMUM SPEED 4200RPM 3600 RPM IDEAL ...

Page 3: ...O electrical load on the generator By using this setting you will have approximately 60HZ cycles or 3600 RPM when you are running at full rated load One way this can be accomplished is by using a Photo Tachometer on our generator shaft A Photo Tachometer is an inexpensive tool that can be purchased at McMasters Grainger Sears or any other electrical supplier ...

Page 4: ...n rotation speed This must be kept as constantly as possible on its nominal value no matter what the load Drive motor speed control systems generally have a small drop in speed between no load and loaded conditions We therefore recommend setting no load speed 3 4 above nominal speed CHECKING VOLTAGE All the machines are regulated during factory testing If voltage readings differ from the value ind...

Page 5: ...Fabco Power Instruction Manual Page 5 ...

Page 6: ...Fabco Power Instruction Manual Page 6 ...

Page 7: ...place LOW NO LOAD VOLTAGE 1 Speed too low 2 Faulty rotary diodes 3 Breakdown in windings 4 Capacitor with high capacity 1 Check and adjust RPM s 2 Check and replace 3 Check winding resistance as per tables 4 Check and replace PROPER NO LOAD BUT LOW LOADED VOLTAGE 1 Low loaded speed 2 Load too large 3 Rotary diodes short circuited 1 Check and regulate RPM 2 Check and change 3 Check and replace UNST...

Page 8: ......

Reviews: