6.4 DUCTS SET-UP
1
2
3
Figure 10 - Cable Diagram for entry lane
Pos. Type
Device
Type of cable
Section
1
P
ower Supply (Vac)
Station
Flame-retardant
2
x 1.5 mm² + ground
2
Data
Station
T
CP/IP:
U
TP cat.5 or higher
8
x 0.2 mm²
3
Data
I
ntercom system (analog/
VOIP)
A
nalog:
T
wisted pair
0
.4 mm² (275 Ω/Km)
0
.6 mm² (122 Ω/Km)
P
rovide separate conduits by connection type:
▫
VAC mains supply
▫ VDC power supply
▫ magnetic loops
▫
data line
U
se the dimensions of the cable cross-sections shown in the table to calculate the size of the conduits to be installed.
It is essential to provide separate channels for mains voltage (230 VAC power cables) and low voltage
(cables: control, safety, intercom, serial data line, etc.)
Summary of Contents for PARQUBE APS
Page 2: ......
Page 7: ...7 68 Ver 1 1 January 2017 en US Chapter 1 MANUAL INTRODUCTION ...
Page 10: ...10 68 Ver 1 1 January 2017 en US This page is intentionally left blank ...
Page 11: ...11 68 Ver 1 1 January 2017 en US Manual introduction Chapter 2 GENERAL CONDITIONS ...
Page 17: ...17 68 Ver 1 1 January 2017 en US Chapter 3 STORAGE AND HANDLING ...
Page 24: ...24 68 Ver 1 1 January 2017 en US This page is intentionally left blank ...
Page 25: ...25 68 Ver 1 1 January 2017 en US Chapter 4 PRODUCT DESCRIPTION ...
Page 36: ...36 68 Ver 1 1 January 2017 en US This page is intentionally left blank ...
Page 37: ...37 68 Ver 1 1 January 2017 en US Chapter 5 ACCESS TO THE PERIPHERAL ...
Page 42: ...42 68 Ver 1 1 January 2017 en US This page is intentionally left blank ...
Page 43: ...43 68 Ver 1 1 January 2017 en US Chapter 6 INSTALLATION ...
Page 60: ...60 68 Ver 1 1 January 2017 en US This page is intentionally left blank ...
Page 61: ...61 68 Ver 1 1 January 2017 en US Chapter 7 SETTINGS ...
Page 64: ...64 68 Ver 1 1 January 2017 en US This page is intentionally left blank ...
Page 65: ...65 68 Ver 1 1 January 2017 en US Chapter 8 DECLARATION OF CONFORMITY ...
Page 67: ...67 68 Ver 1 1 January 2017 en US This page is intentionally left blank ...
Page 68: ...HUB Parking Technology a Business Unit of the FAAC Group www hubparking com ...