Door Controller
22
532226 - Rev. D
EN
Translation of the original instructions
• INPUTS
There are 3 inputs available at the terminal (J14), which can be activated by
connecting them to GND via a “volt free contact” (e.g. a relay).
The inputs will be configured automatically according to the configuration of
the device (see table):
Configuration
IN1
IN2
IN3
Reading point
Configurable
Configurable
Configurable
Pedestrian Passage
Configurable
Transit
Configurable
Vehicle Access
Presence Reader A
Transit
Configurable
Bi-directional Vehicle Access
Presence Reader A
Transit
Presence reader B
Door manager
Door state
Door opener
Configurable
5
• OUTPUTS:
There are 2 double contact (N.O. and N.C.) relay outputs available (RL1 - RL2)
at the terminal (J10).
The maximum current that can be connected to the contacts is 10A at 250 Vac.
!
WARNING !!
Place a suitably rated protective device (e.g. a fuse), between the relay con-
tacts and the load and which anyway does not exceed a maximum of 10A.
Reading point connection example
Door
Controller
XKPR