background image

E024S 

     10 

         732642 - Rev. F

7.1 

 SETTING THE BUS PHOTOCELLS

  

Important to give both the transmitter and the 

receiver the same address.

 Make sure that there are not two or more pairs 

of photocells with the same address.

 If no BUS accessory is used, leave the BUS con-

nector free (J10 - fig. 1).

PAIR

Dip1

Dip2

Dip3 Dip4

Ref.

Type

1

OFF

OFF

OFF

OFF

B -C

OPENING

2

OFF

OFF

OFF

ON

3

OFF

OFF

ON

OFF

4

OFF

OFF

ON

ON

5

OFF

ON

ON

OFF

6

OFF

ON

ON

ON

7

ON

OFF

OFF

OFF

D

CLOSING

8

ON

OFF

OFF

ON

9

ON

OFF

ON

OFF

10

ON

OFF

ON

ON

11

ON

ON

OFF

OFF

12

ON

ON

OFF

ON

13

ON

ON

ON

OFF

14

OFF

ON

OFF

OFF

A

OPENING 

and CLOSING

15

OFF

ON

OFF

ON

16

ON

ON

ON

ON

/

OPEN PULSE

Tab. 3 - Setting of bus photocells

Table 3 shows the programming operations of the dip-switch 
inside the transmitter and of the BUS Photocells receiver.

A maximum of 16 BUS photocell pairs can be connected to 
the board.
The photocells are split into groups:

Opening photocells: 

 

 

max 6

Closing photocells: 

 

 

max 7

Opening /Closing photocells:   

max 2

Photocell used as an OPEN pulse: 

max 1

Fig. 2 shows a 2-swing leaf automated system indicating the 
coverage beams of the photocells:
A:  Photocells with OPENING and CLOSING action.
B:  Photocells with OPENING action
C:  Photocells with OPENING action
D:  Photocells with CLOSING action

6.3.5  RETURN TO DEFAULT SETTINGS

Restore the default settings as follows: 

1.  Keep the SETUP push-button pressed to switch the board ON.

2.  Both SETUP LEDs are alternately lit

3.  The board resets the parameters.

4.  Until the SETUP push-button is pressed, movements are inhibited.

5.  When the SETUP push-button is released, both LD4 and LD5 

LEDs flash.

6.  The default configuration is reset and the new Setup can be 

started.

Fig. 2

6.3.6 PARAMETER DEFINITION

-   

Anti-wind

: the anti wind function enables the gate to operate

 

   even if there are gusts of wind. The obstacle detection time is   

 

   set to 5 s and commands the reversal of motion. 

 Reversing stroke:

  when the gate is closed, the reversing stroke

 

   function makes it possible that before the opening movement,

 

   the motors push to close for approx. 3 s to facilitate uncoupling

 

  the electric lock.

-  

Soft-touch

: the soft touch function makes it possible that, after 

 

   touching the closing limit stop,  the leaves reverse and then

 

   rest gently. This function can be useful to observe the impact 

 

   curve as requested by current standards.

-  

Pre-flashing:

 it activates approx. 3 s before every opening

 

    and closing movement 

-  

Leaf delay at opening:  

it delays the leaf 2 start at opening 

 

   with respect to leaf 1, avoiding thus any interference between

 

   the leaves.

-  

Leaf delay at closure: 

it delays leaf 1 at closure with respect 

 

   to leaf 2.

-  

Pause time

: In logic A it is the time set for the leaf re-closure

 

   after the opening.

- Stop point search space:

  this  parameter  adjusts  the 

mechanical stop search angle within which the board stops 
the movement without reversing if an obstacle is encountered 
or the mechanical stop itself can be adjusted.  

 7 

INSTALLATION OF BUS ACCESSORIES

This  board  is  supplied  with  a  BUS  circuit  enabling  easy  con

-

nection of a high number of BUS accessories (e.g. up to 16 
photocells pairs), appropriately programmed, using only two 
cable without polarity.
Below  we  describe  the  addressing  and  memory  storage  of 
the BUS photocells.
For other future accessories, refer to the specific instructions.

ENGLISH

Summary of Contents for E024S

Page 1: ...E024S...

Page 2: ...ETUPS MUSS MIT DEN DIP SWITCHES DS1 DS3 DS4 DER AN DIE ANLAGE E024S ANGESCHLOSSENE ANTRIEB ANGEW HLT WERDEN ANLEITUNGEN BER ALLE ANDEREN EINSTELLUNGEN SIND DER BETRIEBSANLEITUNG E024S ZU ENTNEHMEN ATE...

Page 3: ...Bologna 10 11 2014 CEO A Marcellan INDEX BOX LAYOUT 4 1 WARNINGS E024S 5 2 LAYOUT AND CONNECTIONS E024S 5 1 WARNINGS E024S FITTED ON 391 6 2 LAYOUT AND CONNECTIONS E024S FITTED ON 391 6 3 TECHNICAL SP...

Page 4: ...e box are shown in Fig A The cover hinges can be moved upward to allow opening the box housing Fig C they can also be removed and re posi tioned in order to enable the cover to open to the right or le...

Page 5: ...rate power cables from control and safety cables push button receiver photocells etc To avoid any electrical disturbance use separate sheaths or a shielded cable with the shield earthed CONTROL UNIT E...

Page 6: ...wer cables from control and safety cables push button receiver photocells etc To avoid any electrical disturbance use separate sheaths or a shielded cable with the shield earthed CONTROL UNIT E024S fi...

Page 7: ...o shut down 4 OPEN B Device with N O contact 5 OPEN A J10 RED terminal BUS Safety devices with BUS technology J2 GREY terminal SERVICE LIGHT on for 90 sec following movement Service Light control outp...

Page 8: ...utomatically During the Setup phase both LEDs flash The leaves start to open one at a time from any position till they detect the opening limit stop Next the leaves start to close one at a time till t...

Page 9: ...t stop is detected it is set as leaf 1 closing stop point if an open command is detected it is set as leaf 1 closing stop point If the SETUP procedure is performed correctly the LD4 and LD5 LEDs turn...

Page 10: ...push button is released both LD4 and LD5 LEDs flash 6 The default configuration is reset and the new Setup can be started Fig 2 6 3 6 PARAMETER DEFINITION Anti wind the anti wind function enables the...

Page 11: ...memory store total opening OPEN A or partial opening OPEN B and by holding it down press the push button SETUP SW1 6 The LED on the board lights up on steady beam for 1 second and then goes OFF indic...

Page 12: ...ing OPEN B and as you hold it down also press the SETUP SW1 push button The relevant LED starts to flash slowly for 5 sec 3 Release both push buttons Within these 5 sec press the appropriate push butt...

Page 13: ...e recognised during bus device acquisition chapter 7 2 The use of this type of encoder offers precise and constant information on leaf position guaranteeing reverse movement in case of obstacles The e...

Page 14: ...orrect coupling of the encoder with the leaf as indicated in the following figure LED ON FLASHING OFF DL 1 Power supply on and BUS connected to board Power supply on but BUS not connected No power sup...

Page 15: ...The closing photocells reapply the pause E Semiautomatic an OPEN pulse opens the gate and the following one closes it An OPEN pulse stops the gate when opening and reopens when the gate is closing The...

Page 16: ...at release OPEN stops saves CLOSE OPEN recloses leaves immediately 1 recloses leaves immediately no effect OPEN CLOSE disabled no effect no effect CLOSE disabled no effect OPEN CLOSE disa bled CLOSIN...

Page 17: ...loses after 5 s stops and opens at release saves CLOSE OPEN IN PAUSE recharges pause time 1 recharges pause time 1 stops operation no effect stops and closes on release after 5 s recharges pause time...

Page 18: ...79 6645 faactm info faacgroup com www faac de INDIA FAAC INDIA PVT LTD Noida Delhi India tel 91 120 3934100 4199 www faacindia com IRELAND NATIONAL AUTOMATION LIMITED Boyle Co Roscommon Ireland tel 35...

Reviews: