The installer is responsible for grounding the operator 

system, for providing the main power breaker switch, 

and for making sure that the entire gate system meets 

all applicable electrical codes. 

J4

J1

J3

F1

F2

PE N L

MAIN

1

2

4

5

6 7 8

COM OP

M1

COM OP

M2 CL

LAMP

9 10 11 12 13 14 15 16 17 18 19

OPEN

A

B STP CL OP

FSW

-

-

-

+24V

+

+

-TX

FSW

20 21

W.L.

LOCK

J5

J2

F

22

23

24 25

FC

A1

FC

C1

FC

A2

FC

C2

+

STOP

OP_A

OP_B

FSWCL

FSWOP

FCC1

FCC2

FCA1

FCA2

J6

F

F1

F2

J1

J2

J3

J4

J5

J6

DL

+

Input Voltage

115 V~ ± 10% or 

230 V~ +6%  -10%   

50/60 Hz

Input Power

10 W

Motor Max. Load

800 W

Accessories Max. Load

0,5 A

Electric Lock Max. Load

15 VA

Ambient Operating Temperature Range

-4°F to +131°F

Protection Fuses

5A  (230V version)
10A (115V Version)
800 mA (accessory)

DL

  STATUS AND PROGRAMMING DISPLAY

J1

   LOW VOLTAGE TERMINAL BLOCK

J2

   CONNECTOR FOR RADIO RECEIVER

J

3   

AC POWER SUPPLY TERMINAL BLOCK

J4

   MOTORS AND WARNING LAMP TERMINAL BLOCK

J5

   INDICATOR-LIGHT AND ELECTRIC LOCK TERMINAL BLOCK

J6

   LIMIT-SWITCH TERMINAL BLOCK

F1

   MOTORS AND TRANSFORMER PRIMARY WINDING   

 

       FUSE (F 5A - 230V) (F 10A - 115V)

F2

   LOW VOLTAGE AND ACCESSORIES FUSE (T 800mA)

F     

“F”  PROGRAMMING PUSH-BUTTON

 –     

“–”  PROGRAMMING PUSH-BUTTON

+     

“+”  PROGRAMMING PUSH-BUTTON

3. Features

Function Logics

Semi-automatic / Automatic / Safety Devices / “Stepped” Semi-

automatic / “Stepped” Automatic / “Stepped” Safety Devices  / 

Semi-automatic B / Dead-man C

Opening/Closing Time:

Programmable (from 0 to 120 s)

Pause Time:

Programmable (from 0 to 4 min.)

Closing Leaf Delay:

Programmable (from 0 to 4 min.)

Opening Leaf Delay:

2 s (can be excluded)

Thrust Force

:

Adjustable on 50 levels for each motor

Terminal Board Inputs

Open / Open Free Leaf / Stop / Limit-switch / Opening Safety Devices 

/ Closing Safety Devices / Power Earth.

Terminal Board Outputs

:

Flashing Lamp / Motors / 24 VDC Accessories Power Supply / 24 VDC 

Indicator-Light / Fail Safe / 12 VAC Electric Lock Power Supply

Programmable Functions

Logic / Pause Time / Thrust Force / Torque at Initial Thrust / Opening and 

Closing Leaf Delay / Reversing Stroke / Over-Pushing Stroke / Indicator-

Light /  Pre-Flashing / Electric Lock / Fail Safe / Safety Devices Logic 

/ Assistance Request / Detection Time of Obstacle or Contact Point

Learning Function

:

Simple or complete work time learning, with or without Limit-switches

Terminal Block J3 - Power Supply

PE:

 

Earth Connection / Ground

N: 

AC

 

V~ power supply (Neutral)

L: 

AC V~ power supply (Line)

Connector J2 - Rapid Connection to RP Receivers

455 D

RP 418 DS

RP 433 RC

1. General Description

The 455 D control board is used to operate the FAAC High 

Voltage swing gate operators. It has several operating logics 

built in, programmable with the help of a display and push-

buttons. The board allows connection of various accessories 

including monitored photocell for compliance with the 

UL325 standard Ed: 7. 

The 455D control board allows the connection of 1 close 
and up to 2 open entrapment protection devices. 

The board should be installed in an enclosure that is con-

veniently located as close as possible to the gate operator. 

All electrical connections from the control board to the 
operator must be made in a weatherproof junction box.

The 5 pin J2 connector allows to plug in the FAAC RP radio 

receivers

455D CONTROL BOARD

2. Technical Specifications

4. Layout and Components

Summary of Contents for 750 Standard

Page 1: ...Operator FAAC International Inc Headquarter East Coast Operations 3160 Murrell Road Rockledge FL 32955 Tel 800 221 8278 www faacusa com FAAC International Inc West Coast Operations 357 South Acacia A...

Page 2: ...draulic Connection 9 2 5 Air Bleed Operations 10 2 5 Installing The Gate 11 3 FINAL OPERATIONS 12 3 1 Adjusting the By Pass Valves 12 4 MANUAL OPERATION 12 5 MAINTENANCE 12 455D CONTROL BOARD 1 Genera...

Page 3: ...an usage Locate the gate such that persons will not come in contact with the vehi cular gate during the entire path of travel of the vehicular gate c The gate must be installed in a location so that e...

Page 4: ...ipment may reach high thermal temperatures during normal operation therefore use caution when touching the external housing of the gate operator Use the manual release mechanism according to the proce...

Page 5: ...factory or loa ding dock area or other locations not accessible by or intended to service the general public CLASS IV RESTRICTED ACCESS VEHICULAR GATE OPERATOR A vehicular gate operator or system int...

Page 6: ...P OIL Operating ambient temperature 4 F 131 F 20 C 55 C Protection class IP 55 Weight 16 5 lb 7 5Kg Pump capacity 0 75 l min Max leaf length 13 ft 4 m Min leaf length 8 ft 2 4 m 1 Exposure to direct s...

Page 7: ...keep a minimum distance between the rotation axis of the hinge and the post of 2 4 in 60mm fig 6 a Insure that the cavity where the drive unit is located is well drained by means of pipes gravel drai...

Page 8: ...r the two hydraulic lines that run from the drive unit to the power unit 8 Weldtheboxhalvestothefoundationplateandtooneanother so as to enclose the drive unit on four sides Be sure to protect the driv...

Page 9: ...hydraulic control unit fig 13 C A B D CLOSE OPEN INT EXT 12 1 2 3 4 A B C D E 13 The control unit fitting beside the green by pass screw must be connected to the drive unit fitting that is within the...

Page 10: ...and loosen the air bleed screw for the closing movement fig 12 ref C as shown in fig 16 7 release any air from the hydraulic circuit until non emulsified oil appears 8 tighten the air bleed screw befo...

Page 11: ...e rotation axis fig 18 Spot weld the bushing to the U section Check that the system setup is correct by manually simulating complete opening Carefully weld the bushing to the section fig 19 Close the...

Page 12: ...ed to set of the bypass valve tripping threshold The red screw adjusts the closing pressure of the leaf The green screw adjusts the open pressure of the leaf To increase pressure turn the screws clock...

Page 13: ...This page is intentionally left blank 13...

Page 14: ...n be excluded Thrust Force Adjustable on 50 levels for each motor Terminal Board Inputs Open Open Free Leaf Stop Limit switch Opening Safety Devices Closing Safety Devices Power Supply Earth Terminal...

Page 15: ...connected to this input See the next paragraph on how to connect a monitored device If this input is active when the gate is open it will prevent the leaf closing movement OP FSW Opening safety devic...

Page 16: ...e connected for the system to work 1 2 5 4 3 1 2 RX CL TX CL 9 10 11 12 13 14 15 16 17 18 19 OPEN A B STP CL OP FSW 24V TX FSW 20 21 W L LOCK 1 2 5 4 3 1 2 RX OP TX OP 1 2 5 4 3 1 2 RX CL TX CL 9 10 1...

Page 17: ...act Typically these photocells work in combination with other monitored photocell pro tecting closing or opening entrapment zones In that case they can t be monitored so they can only protect against...

Page 18: ...ill display the param eter s current value Value can be modified with keys and Press and hold F again the unit will display the name of the next function parameter When you reach the last function pre...

Page 19: ...nd OFF when gate is closed the output is ON when the gate is open or in pause OFF in all other conditions the output is ON when the gate is closed OFF in all other conditions All other values correspo...

Page 20: ...and black wires on the 455 D control board 7 Check force setting of the motors modify if necessary Note For hydraulic operators like the 400 force should be programmed to maximum level 50 8 Stop leaf...

Page 21: ...2 stops at opening and immediately begins its closing movement 5 Slow down at closing of leaf 2 6 Leaf 2 stops at closing and leaf 1 begins its closing movement 7 Slow down at closing of leaf 1 8 Leaf...

Page 22: ...i t n o c e s a e l e r n o d n a s k c o L g n i n e p o D E K C O L 3 f a e l e h t s e s o l C t c e f f e o N d e l b a s i d N E P O t c e f f e o N t c e f f e o N d e l b a s i d N E P O E c i...

Page 23: ...diately stops operation NB Effects on other active pulse inputs in brackets P A c i g o L S E S L U P S U T A T S E T A G A N E P O B N E P O P O T S S E C I V E D Y T E F A S G N I N E P O S E C I V...

Page 24: ...OR 1 MOTOR 2 CL COM OP 1 2 3 4 5 6 7 8 20 21 FCA1 FCA2 FCC2 FCC1 F J2 J6 J4 J5 J3 N L MAIN OP CL 24 V FSW B STOP A TX FSW 9 10 11 12 13 14 15 16 17 18 19 J1 PHOTO OP OPEN DEVICES PHOTO CL 24VDC RX PHO...

Page 25: ...prewired enclosure comes with dedicated terminal blocks for the connection of safety photocells that can be monitored by the control board for presence and correct operation One closing and one openi...

Page 26: ...ections If using non FAAC relay make sure the minimum switch volt age is less than 12Vac SHADOW INPUT Line Voltage MOTOR ON 24 VDC SHADOW LOOP 120V or 230 AC SHADOW KIT OPTION 8 7 10 1 2 5 Shadow Loop...

Page 27: ...This page is intentionally left blank 27...

Page 28: ...223205 Half Box Part Part Number Description 21 7011085 Bolt 750 Drive Body 8 x 100 mm 22 703108 Lock Washer 23 7366245 Cylinder 750 Drive 100 Degree 24 7090170015 O Ring 66 40 x 1 78 mm 25 7170285 Le...

Page 29: ...ber Description 26 703013 Washer 27 701039 Allen Bolt 4x6 mm 28 4180225 Manual Release 29 7090050015 O Ring 10 82 x 1 78 mm 30 7049135 Valve Retaining Ring Nut 31 4404065 Inlet Valve 32 4404085 Lock V...

Page 30: ..._________________________________________________________ _________________________________________________________________________________________ ____________________________________________________...

Page 31: ...s been subject to misuse negligence or accident or has not been oper ated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe tha...

Page 32: ...2018 FAAC International Inc All Rights Reserved Published in July 2018 750 732028 Rev B US...

Reviews: