Terminals  “16-19”.  Any device (e.g. push-button, remote control,
etc.) can be connected to this circuit.
By closing a contact, the circuit generates a pulse for total
opening and/or closing  of the gate. Its operating mode is set
by dip-switch 3 – see the relevant paragraph.
N.B.: an OPEN-A pulse during the pedestrian stage always has
priority over that stage
N.B.: to install several pulse generators, connect the contacts in
parallel.

Photocells

Terminals  “17-19”.  Any safety device (e.g. photocell, sensitive
strip, etc.) can be connected to this circuit. By opening  a
contact, the circuit  protects closing motion.  The status of this
input is signalled by the FTO LED. It also has an effect on opening
motion, depending on how dip-switch 4 was set – see relevant
paragraph.
N.B.:  If safety devices are not connected, fit a jumper at input.
To install several safety devices, connect the NC contacts in
series.

STOP

Terminals  “18-19”. Any device (e.g. push-button, remote control,
etc.) can be connected to this circuit.
By opening  a contact, the circuit  stops gate movement.  The
status of this input is signalled by the STOP LED.  The set  cycle will
restart only if a successive opening or closing pulse is received.
N.B.: If STOP devices are not connected, fit a jumper at input.
To install several  STOP devices, connect the NC contacts in series.

6. FITTING  DECODING/RP RECEIVER CARDS

Installation procedure: turn off power and fit the module in
container M5 inside the control unit. Then observe the radio-
receiver instructions to store data on the remote-control. After
the necessary data has been stored, the remote-control
activates OPEN-A like any other command device.

7. SETTINGS WITH DIP-SWITCH S1

SW1

ELECTRONIC CLUTCH

ON

Maximum force, minimum sensitivity

OFF

Minimum force, maximum sensitivity

SW2

FUNCTION LOGIC

ON

Automatic

OFF

Stepped

SW3

OPERATION OF OPENING COMMAND

ON

One state only at each pulse; open, stop, close, stop, open etc.

OFF

One movement only at each pulse: open, close, open, close, etc.

SW4

OPERATION OF PHOTOCELLS

ON

Stops at opening, restarts on release, stops at closing and reverses

OFF

Stops and reverses at closing only

SW5

REVERSE PULSE

ON

Generates a pulse for 1.5 seconds at closing

OFF

Disabled

SW6

TIME DIFFERENCE BETWEEN MOTOR 1 AND MOTOR 2

ON

2 seconds at opening, 12 seconds at closing

OFF

2 seconds at opening, 4 seconds at closing

SW7

GATE

ON

Twin-leaf: two gearmotors connected

OFF

Single-leaf: one gearmotor connected

8. CONTROL LEDS

LED

LIGHTED

OFF

POWER - 

power

with  transformer

on battery (if used)

FTO - 

photocells

photocells not covered

photocells covered

STOP - 

stop

command  inactive

command active

N.B.: LED status shown in bold with gate closed and control unit
powered.

9. PROGRAMMING

Programming of work times, deceleration and electronic clutch
is executed during self-learning. At this stage, leaf movement is
at slow speed.

Important: the self-learning procedure must be executed with
back-up batteries (optional) disconnected.

Procedure:
1) Release the leaves, take them to about midway  through

opening travel, and then lock them.

2) Power up the control unit (power ON is signalled by the POWER

LED).

3) Turn switch 

S2

 to 

PROG

: the flashlight goes on at steady light

to signal programming.

4) Press the push-button connected to the OPEN-A terminals or

the  remote-control, if already programmed. The first operation
the automation performs must be CLOSING. First, the leaf
connected to M2 closes, and then the one connected to
M1.

5) If the leaves move to open, touch the two RESET pins with a

screwdriver – the control unit will immediately stop the
movement generated by the automation.

6) Cut power to the control unit,  reverse polarity of the two

cables powering the motors which had supplied opening
drive, and repeat the operation at point 1.

7) After the OPEN-A command is given, the leaves move to close,

until they reach the closing gate stop.

8) After about two seconds, the leaf connected to M1 restarts

opening automatically, and after another two seconds, the
leaf connected to M2 also restarts until it reaches the opening
gate stops.

9) The control unit begins counting pause time. After the required

time has elapsed, press the OPEN-A command again, and
the leaf connected to M2 restarts closing. After the set time
difference has elapsed, the leaf connected to M1 restarts too
until it reaches the closing gate stops.

10)Programming is now finished. Turn switch 

S2

 back to 

OFF

  –

the flashlight goes off.

10. OPERATION OF ELECTRONIC CLUTCH

This is a very important device for safety. Its setting does not alter
through time, as the device is not subject to wear or setting
changes.
It is active both at closing and opening. When it operates it
reverses motion direction without  inhibiting automatic closing if
enabled.
If it operates twice in succession, it moves to STOP position,
disabling any automatic command.
This is why: if the clutch operates twice, this means the obstacle
is still present and any further manoeuvres could be dangerous,
thus obliging the user to give an opening or closing command.
In that case the control unit executes an EMERGENCY proce-
dure as follows: full opening at slow speed up to the opening
gate stop, followed by automatic closing to enable the gate
stops to re-synchronise independently.

11. FUSES

FUSE

PROTECTING

F1 

=

 

F 3.15A 250V 5x20

Logic  /  Accessories  output

F2

 =

 

T 10A 250V 5x20

Motor

Summary of Contents for 424 MPS

Page 1: ... E R TIF I C A T A UNI EN ISO 9001 085 para la naturaleza 100 papel reciclado ist umweltfreundlich 100 Altpapier pour la nature papier recyclé 100 for nature recycled paper 100 carta riciclata 100 per la natura 424 MPS 424 MPS ...

Page 2: ...ni 1 40069 Zola Predosa BOLOGNA ITALY Declares that Electronic appliance 424MPS conforms to the essential safety requirements of the following directives 73 23 EEC and subsequent amendment 93 68 EEC 89 336 EEC and subsequent amendment 92 31 CEE and 93 68 EEC Additional information This product underwent tests in a typical uniform configuration all products manufactured by FAAC S p A Bologna 01 Jan...

Page 3: ...uilt in LEDs constantly indicate status of both control unit and gearmotor The control unit is designed for installation in a watertight outdoor use container which is also designed to house 2 optional batteries and a toroidal transformer with the characteristics shown in the table below 2 CONNECTION LAY OUT MICROPROCESSOR CONTROL UNIT FOR 24 Vdc SWING LEAF GATES 1 2 3 4 5 6 1 7 2 3 4 5 6 PROG OFF...

Page 4: ...rmotor 1 If the gate has one leaf only the pulse partly opens the leaf 50 of work time N B an OPEN A pulse during the pedestrian stage always has priority over that stage N B to install several pulse generators connect the contacts in parallel 3 TECHNICAL SPECIFICATIONS Supply voltage of transformer 230V 6 10 50Hz Supply voltage of control unit 22V 6 10 50Hz Power consumption 3 W Motor max load 2 ...

Page 5: ...ocells covered STOP stop command inactive command active N B LED status shown in bold with gate closed and control unit powered 9 PROGRAMMING Programming of work times deceleration and electronic clutch is executed during self learning At this stage leaf movement is at slow speed Important the self learning procedure must be executed with back up batteries optional disconnected Procedure 1 Release...

Page 6: ...papier pour la nature papier recyclé 100 for nature recycled paper 100 carta riciclata 100 per la natura Le descrizioni e le illustrazioni del presente manuale non sono impegnative La FAAC si riserva il diritto lasciando inalterate le caratteristiche essenziali dell apparecchiatura di apportare in qualunque momento e senza impegnarsi ad aggiornare la presente pubblicazione le modifiche che essa ri...

Reviews: