No.
Task
Description
are missing, contact Extreme Networks
support.
7.
Make sure that the power cord has the
correct country-specific termination.
Power cord types and order codes
page 14.
8.
Prepare the rack.
Ensure that there is enough rack space to
accommodate a 1RU switch (4.45 cm).
Ensure that the rack is bolted to the floor and
braced if necessary.
Ensure that the rack is grounded to the same
grounding electrode used by the power service
in the area. The ground path must be
permanent and must not exceed 1 Ohm of
resistance from the rack to the grounding
electrode.
March 2020
Installing the VSP 7200 Series
17