background image

3 - 5%

Max 3 mt

8

ENGLISH

ExAMPlEs of coRREcT connEcTion To ThE chiMnEy

In the presence of type B gas appliances with intermittent operation not intended for heating, they must have their own aeration and/or 

ventilation opening. 
The air inlets must meet the following requirements:

 

Š

they must be protected with grids, metal mesh, etc., but without reducing the net useful section;

 

Š

they must be made so as to make the maintenance operations possible;

 

Š

positioned so that they cannot be obstructed;

The clean and non-contaminated air flow can also be obtained from a room adjacent to that of installation (indirect aeration and 

ventilation), as long as the flow takes place freely through permanent openings communicating with the outside.

The adjacent room cannot be used as a garage, or to store combustible material or for any other activity with a fire hazard, bathroom, 

bedroom or common room of the building.

Flue gas eXhaust

The heat generator works in depression and is equipped with an outlet fan for flue gas extraction. There must be a single exhaust system for 

the generator. Using a flue that is shared with other devices is not allowed.

The components of the flue gas exhaust system must be chosen in relation to the type of appliance to be installed in compliance with:

 

Š

UNI/ TS 11278 in the event of metal chimneys, with particular attention to that stated in the specification; 

 

Š

UNI EN 13063-1 and UNI EN 13063-2, UNI EN 1457, UNI EN 1806 in the event of non-metallic chimneys.

 

Š

The length of the horizontal section must be minimal and, in any case, no longer than 3 metres, with a minimum upward slope of 3%

 

Š

There must not be more than 4 direction changes including the one due to the use of the "T" element.

 

Š

A “T” fitting with a condensation collection cap must be provided at the base of the vertical section.

 

Š

If the exhaust is not inserted in an existing flue, a vertical section with a windproof end piece is required (UNI 10683).

 

Š

The vertical duct can be inside or outside the building. If the smoke duct is inserted in an existing flue, it must be certified for solid fuel.

 

Š

If the smoke duct is outside the building, it must always be insulated.

 

Š

The smoke ducts must have at least one airtight inlet for flue gas sampling.

 

Š

All the sections of the flue gas duct must be accessible to inspection.

 

Š

Inspection openings must be provided for cleaning.

 

Š

If the generator has a fume temperature lower than  160°C+ ambient temperature caused by the high yield (contact technicians) it 

MUST be resistant to humidity.

 

Š

A flue system that does not respect the previous points or, in general, that does not comply with the regulations, may cause condensation 

phenomena inside it.

ChIMneY CaP

The chimney caps must meet the following requirements:

 

Š

they must have a useful outlet section no less than double that of the chimney/ducted system on which it is installed;

 

Š

they must be adapted in order to prevent the penetration of rain and snow in the chimney/ducted system;

 

Š

they must be built so that, in the event of winds coming from all directions and from any angle, the expulsion of combustion products 

is in any case ensured;

Protection from rain 

and wind

Condensation-proof 

"T" fitting with 

inspection plug 

Insulated flue

Insulated "T" 

fitting with 

inspection plug

Protection from rain and wind

"T" fitting with 

i n s p e c t i o n 

plug

COnneCtIOn tO the MaIns eleCtrIC suPPlY

The generator is supplied with an electric power cable to be plugged into a 230V 50 Hz socket, possibly with a circuit breaker switch. The 

socket must be easily accessible.

The electrical system must be compliant with standards. The efficiency of the earthing circuit must be checked. Unsuitable earthing of the 

system can cause malfunctioning for which the manufacturer will not be held liable. 

Power supply variations beyond 10% can cause faulty operation of the product.

FOr gerManY OnlY

the product can be connected to a shared flue

 (multi-connection) provided that the requirements of the regional and national regulations, 

amongst which DIN EN 13384-2, DIN V 18160-1, DIN 18896 and of the MFeuV-2007 (Muster-Feuerungsverordnung) are strictly complied with, 

and that the local chimney sweep has checked and approved the installation conditions. 

Please also remember the following indications, which the end user must comply with:

• 

The device can be operated only with the doors closed.

• 

The doors and all setting devices must remain closed when the device is not on (except for cleaning and maintenance operations).

Summary of Contents for ANGY

Page 1: ...MADE IN ITALY design production ANGY UK pellet stoves USER MANUAL 004281159 Rev 000...

Page 2: ...2 ENGLISH APPLY TECHNICAL DATA LABEL...

Page 3: ...AUTOMATIC 23 AUX 23 settings 24 DISPLAY 24 STAND BY 24 OPERATION WITH ADDITIONAL THERMOSTAT OPTIONAL 24 Delta t 25 FIRST LOAD 25 RESET 25 EASY CONTROL 25 wi fi 25 Operation and SOLUTIONS 26 RADIO PRO...

Page 4: ...ance has been installed as well as the instructions contained in this manual The use of the appliance must comply with all local regional national and European regulations The Manufacturer cannot be h...

Page 5: ...IF IT IS DISCONNECTED FROMTHE MAINS It is advised to position the power supply cable so that it does not come into contact with hot parts ofthe appliance The power supply plug must be accessible afte...

Page 6: ...clean the majolicas it is recommended to use a soft dry cloth If a detergent or liquid is used the latter could penetrate inside the crackles highlighting them SINCE THE PRODUCT CAN TURN ON AUTOMATICA...

Page 7: ...mestichotwaterproductionandinadjacentandcommunicating rooms 3 where the depression measured in situ between the external and internal environment is greater than 4 Pa N B Watertight appliances can als...

Page 8: ...always be insulated The smoke ducts must have at least one airtight inlet for flue gas sampling All the sections of the flue gas duct must be accessible to inspection Inspection openings must be prov...

Page 9: ...installed This means that it is ideal for passive houses because it does not take air in from within the house combustion air To ensure the stove remains hermetically sealed the connection pipe for th...

Page 10: ...A Access to combustion chamber and ash drawer E Rear fumes exhaust G On Off B Pellet hopper pressurised closure F Serial input fuse C Room air outlet 230V power supply Supplementary thermostat input D...

Page 11: ...will cause the display to show the following CLOSE HOPPER DOOR This indication means that you have 60 seconds to close the hatch door and the pellet lid Once 60 seconds have passed during ignition th...

Page 12: ...AVAILABLE the conversion of the rear flue gas outlet MUST BE CARRIED OUT BY QUALIFIED PERSONNEL AND OR THE MANUFACTURER S TECHNICIANS J It is forbidden to carry out this assembly and install the appl...

Page 13: ...R QUALITY PELLETS OR ANY OTHER MATERIAL WILL COMPROMISE STOVE FUNCTIONS VOIDING THE WARRANTY AND RELEASING THE MANUFACTURER OF LIABILITY Do not place the bag directly on the stove to load the tank Alw...

Page 14: ...1 Yellow LED LED off radio communication not available LED on radio communication available L4 Yellow LED LED on 5 power set by the user L2 Red LED LED off normal operation LED on alarm present L5 Yel...

Page 15: ...allows calibration of the room temperature detected by the radio control device with ventilation active only For correct calibration it is recommended to position the radio control in a room with cons...

Page 16: ...tment The radio control is fitted with an LCD backlit display The display remains lit for 5 seconds After a certain period of time in order to minimise battery consumption the display turns off sleep...

Page 17: ...AL TA DISPLAY Display text Temperature detected in room Room SET THERMOSTAT set Power 1 5 Time Chrono active STAND BY active Battery low Display text Time Indicates the status of the contact of the ex...

Page 18: ...ents or substances other than those indicated in the manual Before turning on the product it is necessary to perform the following checks If it is intended to be connected to a hydraulic system it mus...

Page 19: ...t OK SETTINGS LANGUAGE DEGREES This menu allows you to set the desired unit of measurement To set OK SETTINGS DEGREES FIRST IGNITION SETTINGS After connecting the power cord at the back of the generat...

Page 20: ...erature probe built into the radio control If the contact is open met the stove operates at the minimum value or it switches off if STAND BY mode is active If the contact is closed request the stove w...

Page 21: ...F THE FIRST TWO ARE INSUFFICIENT SECOND DECREASE RANGE IF THE FIRST IS INSUFFICIENT FIRST DECREASE RANGE TEST FOR 1 DAY OPTIMAL FACTORY VALUE FIRST INCREASE RANGE SECOND INCREASE RANGE IF THE FIRST IS...

Page 22: ...HRONO MODE It allows the user to choose in which MODE see paragraph the stove will be switched on in the set time slots choosing between MANUAL AUTOMATIC AUX PRG 1 4 Prg x allows you to set the igniti...

Page 23: ...X Power Time slot 1 Start 02 00 Stop 23 00 Power 5 02 00 23 00 08 00 16 30 t 02 00 23 00 08 00 16 30 t 5 1 22 2 1 Time slot 2 Start 08 00 Stop 16 30 Power 1 Stove setting if TA contact closed AUTOMATI...

Page 24: ...WORK will be displayed on the screen OPERATION WITH ADDITIONAL THERMOSTAT OPTIONAL STAND BY function set to OFF FACTORY SETTING If the STAND BY function is not active OFF if the stove exceeds the roo...

Page 25: ...of combustion residues in the flue during operation at reduced power see FLUE EXHAUST chapter Caution It is advisable to activate the EASY CONTROL function under the supervision of a qualified technic...

Page 26: ...access firewall issues CLOUD OK The Wi Fi module is connected to the cloud The firmware revision number of the Wi Fi module is also indicated RSSI Wi Fi signal strength when it is correctly connected...

Page 27: ...must be performed by qualified staff and or the manufacturer s service technicians ADDITIONAL FUNCTIONS Additional thermostat INSTALLATION optional The stove can control the room temperature through a...

Page 28: ...ty Cleaning the ceramic glass Never use abrasive or chemically aggressive detergents for cleaning The ceramic glass must be cleaned when the glass is completely cold To clean the ceramic glass simply...

Page 29: ...rom the burn pot housing ignition plug holder tube and combustion chamber Free all the holes in the burn pot using the poker supplied Re position the burn pot in its housing and push it towards the fi...

Page 30: ...works properly They must be controlled periodically They must be replaced immediately if they are worn or damaged These operations must be carried out by a qualified technician CLEANING THE FLUE GAS C...

Page 31: ...d apply silicone where indicated C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and cleaning and check gasket E Check air inlet pipe and...

Page 32: ...tion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and cleaning and check gasket E Check air inlet pipe and check clean mechanical pressure switch F...

Page 33: ...larm The alarm can only be reset if the fumes motor has stopped and 15 minutes have passed since the alarm was displayed by pressing key 1 for 3 seconds Fumes motor Fault Fumes motor fault Contact aft...

Page 34: ...er and the fume pipe of the appliance Clean clear the T shaped fitting the flue pipe and the chimney flue DELTA P FAULT Differential pressure transducer faulty or disconnected Contact after sales cent...

Page 35: ...kindly asked to separate this equipment and or batteries or accumulators included from other types of waste and to arrange for disposal by the municipal waste service It is possible to ask your local...

Page 36: ...45 865911 39 0445 865912 info extraflame it www lanordica extraflame com TO FIND THE SERVICE CENTRE NEAREST TO YOU CONTACT YOUR DEALER OR CONSULT THE SITE WWW LANORDICA EXTRAFLAME COM The manufacturer...

Reviews: