Pg.
10
•
AC loads will be powered by the battery with the inverter if battery voltage is
higher than
11V
.
•
When battery voltage drops below
11V
, the inverter automatically switches to
shore power (if connected) and charges the batteries.
•
When battery is charged to
13.5V
, the inverter will automatically switch back to
battery power.
•
When shore power is not detectable and battery voltage is lower than 10V, the
inverter will shut down. When shore power is detected again, the inverter will turn
on automatically and switch to shore power and charge the battery or when
battery is charged to
12V
, inverter will automatically turn on and switch to battery
power.
When set to DC priority, the inverter will utilize the battery bank for electricity over
shore power. When battery voltage gets too low, it will automatically switch to shore
power if it is connected. Charging can be turned off by setting battery switch to 0.
(See Page 10)
DC Priority
the inverter while simultaneously charging the battery bank this is also known
as the bypass function. Charging can be turned off by setting Battery Type
switch to 0. (See page 10)
•
When shore power is disconnected, the inverter automatically switches to
solar/battery bank power in 5ms.
•
When shore power is restored, the inverter will automatically switch the power
source from battery bank to shore power in 5 ms.
Inverting
Inverter Charger
With
Transfer Switch
AC Breaker Box
AC Load
12V Battery
DC Fuse Block
DC Load
Solar Panel
Solar Charge
Controller
Shore Power
NOT IN USE
When battery voltage is
HIGHER THAN 11V
Inverter Charger
With
Transfer Switch
AC Breaker Box
AC Load
11V Battery
Shore Power
DC Fuse Block
DC Load
Solar Panel
Solar Charge
Controller
Charging
When shore power is connected & battery voltage is
LOWER THAN 11V