13
For output single-channel, the BB=1c, Ac or Bc where c is
the selected channel, and the DD must be 00 to clear output
and 01 to set output.
Parameter for Single-Channel Output
Single channel output command #AABBDD
c for BB=1c/Ac
c for BB=Bc
EX9042D
0 to 7
DO(0~7)
0 to 4
DO(8~12)
EX9043D
0 to 7
DO(0~7)
0 to 7
DO(8~15)
EX9044D
0 to 7
DO(0~7)
NA
NA
EX9050D
0 to 7
DO(0~7)
NA
NA
EX9055D
0 to 7
DO(0~7)
NA
NA
EX9060D
0 to 3
RL(1~4)
NA
NA
EX9063D
0 to 2
RL(1~3)
NA
NA
EX9065D
0 to 4
RL(1~5)
NA
NA
EX9066D
0 to 6
RL(1~7)
NA
NA
EX9067D
0 to 6
RL(1~7)
NA
NA
Response:
Valid Command:
>
Invalid Command:
?
Ignore Command:
!
Delimiter for ignore the command. The module's
host watchdog timeout status is set, and the output
is set to Safe Value.