36
2.24 ~AA4V
Description:
Read Power On/Safe Value
Syntax:
~AA4V[CHK](cr)
~ delimiter
character
AA address
of
reading/response module (00 to FF)
4
command for read Power On/Safe value
V
P= read Power On Value, S= read Safe Value
Response:
Valid Command:
!AA(Data)
Invalid Command:
?AA
(Data) Power On Value or Safe Value
For EX9042D/43D(Data) is
VVVV
,
where VVVV is the Power On Value (or Safe Value).
For other modules, (Data) is
VV00
,
where VV is the Power On Value(or Safe Value).
Example:
Command: @0100 Receive: >
Output address 01 Value 00, return success.
Command: ~015S Receive: !01
Set address 01 Safe Value, return success.
Command: @01FF Receive: >
Output address 01 Value FF, return success..
Command: ~015P Receive: !01
Set address 01 Power On Value, return success.