Spillage test and pressure differential switch
The test should be carried out to ensure that the fan speed and the pressure differential switch (PDS) have
been correctly set for the appliance. This should be made with all the doors and windows closed. If any
extractor fans have been fitted, the test should be made with these fans on. If spillage is detected, the fan
speed must be turned up.
Please refer to the appropriate Exodraft fan control installation guides, for further commissioning
assistance.
Type
PDS Factory setting
RSG150-41
90 Pa
RSG200-41
60 Pa
RSGC150-41
Fix 10/20 Pa
WARNING! Turn the fan off at the isolation switch
before commisioning is startet.
ATTENTION!
•
Open the fan cover for setting the PDS
• Start and run the fan as described in the control manual
•
Be aware that the cooling vane on the motor is running
Reduced fan speed
If...
Then...
the RMS voltage to fan motor is under 160 V
The outlet grill can be adju-
sted in order to enable the
RSG/C to work with low
fan speed and still have the
failsafe system working.
no spillage has been detected
the PDS is adjusted to the factory setting
the fail-safe system sometimes, or always,
turns the gas of
•
There is a plate on the underside for this purpose (see figure).
•
Turn the plate to position II, commission the system as described
above and check with a spillage test.