Example
Air humidity level is
Airflow...
A
less than Start
is the same as set value
B
between Start and Maximum
increases gradually to a high value,
depending on the current air humidity
(RH level)
C
greater than Maximum
is increased to maximum air replace-
ment
Menu 3.1.2.3 - Airflow reduction
Function
When the control system is operating, this function reduces the required supply air
airflow in the event of falling supply air temperature. This makes it possible to
maintain the required supply air temperature longer.
Selecting airflow re-
duction
Activate in Menu 3.1.2.3.
3006401-2022-05-04
Starting up the unit for operation
28/72