Menu 3.4 - Accessories
Ice-detect. >
De-icing method >
Heating coil >
Cooling unit >
Power step HCE >
Filter detect. >
PIR >
TS >
CO2 >
RH >
Dining solution >
3.4 Accessories
Tice
6
None
None
4
Timer
None
None
None
None
No
AUX OUT setting >
1
Line in Menu 3.4
Factory-set and
should not be
changed.
Comments
Ice detection method
● Tice
De-icing method
Selected automatically:
● Method 4, if a heating coil
is present
● Method 6, if no heating
coil is present
Heating unit
Options:
● None
● MHCW (Water heating
coil)
*)
● MHCE (Electric heating
coil)
● IHCW (set at the factory
for the the EXact2 main
board, if the VEX was
purchased with HCW)
*) Not applicable to VEX308
Cooling unit
*)
Options:
● None
*)
● MXCU (external cooling
unit)
*)
● CCW (cold water coil)
*)
● CU (EXHAUSTO cooling
unit)
*)
*) Not applicable to VEX308
Filter detection
● Hours
PIR
Activating PIR sensor. Op-
tions:
● None
● PIR1 (MIOPIR connected)
● PIR2 (PIRB connected)
● Both (Both MIOPIR and
PIRB connected)
When the sensor(s) is/are acti-
vated by movement in the
room, the VEX will be overrid-
den and set to comfort level.
Comfort level will be main-
tained for the time set on the
rear of the sensor (PIRB), af-
ter which the VEX will return to
the previous indoor climate
level.
NB: The time interval for MIO-
PIR is a fixed 10 minutes and
cannot be changed).
3006401-2022-05-04
Starting up the unit for operation
16/72