6.6 Overview of menu structure
MAIN MENUS SUB-MENUS
DESCRIPTION OF FUNCTION
Factory
setting
1 EXIT
Exit from main menu to operational display
2 SENSOR
20 EXIT
Exit to main menu
21 SENSOR MODE
If On is selected: the control unit is now set to operate with a
temperature sensor
If Off is selected: the control unit functions only as a speed
regulator
Off
22 START TEMP
Temperature limit for control to start automatically
setting range 5–100 °C
25 °C
23 STOP TEMP
Temperature limit for control to stop automatically
Setting range: 0–95 °C
20 °C
24 ALARM TEMP
Temperature limit for the control to trigger a chimney fire alarm
Setting range: 100–400 °C
330 °C
3 TIMER
30 EXIT
Exit to main menu
31 BOOST TIME
Timer that makes the chimney fan deliver maximum draw
during cold starts (cold fireplace or stove)
Setting range: 1–15 minutes
7 min.
32 STOP TIME
Timer ensures that all the fuel is completely combusted
Setting range: 1–45 minutes
45 min.
4 ALARM
40 EXIT
Exit to main menu
41 LOG
Display of the five most recent errors or alarms
42 RESET LOG
Deletes all non-active errors in the alarm log
5 NETWORK
50 EXIT
Exit to main menu
51 ADD NODE
Menu used when you are connecting a unit to the network
52 DELETE NODE
Menu used when you are disconnecting a unit from the
network
53 SIGNAL TEST
Menu that keeps the control unit active and allows a commu-
nication check to be run on power and/or repeater units.
54 RECIEVE REPLICATION
Not used (for connecting large networks)
55 SEND REPLICATION
Not used (for connecting large networks)
56 RESET CONTROLLER
Resets the control unit to neutral so the whole system has
to be reinstalled
NB All the nodes (Power Unit and Repeater, if any) must
be deleted (menu 52) before the network is set up again
(menu 51).
6 SERVICE
60 EXIT
Exit to main menu
61 VERSION
The display shows the version of the software installed
62 FACTORY SETTING
Re-establishes all factory settings
63 LANGUAGE
The operational guide can be presented in five languages:
(GB, DK, N, S, D)
GB
64 MIN SPEED
The minimum speed can be adjusted within a limited range:
Setting range: 80–120 Volt.
100 V
7 SETTING
70 EXIT
Exit to main menu
71 CONTRAST
Setting the display: Contrast
70
72 BACKLIGHT
Switch the display light on/off
On
73 SPEAKER
On: an audio signal is emitted when it is time to add new fuel
(refiring).
Off: no audio signal for refiring
On