EXHAUSTO
3001736-2004-01-21.fm
Commissioning
8/12
3.
Commissioning
Commissioning is carried out with the control panel open. Only touch
the components in the box with electrically insulated tools.
Notice
Before commissioning all windows and doors must be closed; if other types of fans are
installed they must be switched on 10 minutes in advance and run at full speed during
commissioning.
Dipswitches
Check the factory settings of the dipswitches (Fig. 1-I) before commissioning.
In service mode the safety functions of the flow control (PDS) and the
fresh air inlet are bypassed
•
Open control panel
•
Press ON/OFF button (Fig. 1-C)
•
Wait until constant green light, if the fire has to be lit during commissioning
•
Press the service mode button (Fig. 1-H) on reverse of front cover. The alarm
LED (Fig. 1-A will flash RED and operation LED (Fig. 1-B) will flash according to
the position of the PDS switch as follows:
Notice
Service mode is turned off next time the ON/OFF button is pressed or after half-an-hour
Dip-
switch
Name
Factory
setting
OFF
ON
1
MANUAL
RESET
ON
Automatic reset
after power fai-
lure and draught
failure.
Manual reset after
power failure and
draught failure
2
AFTER-
VENTILATION
OFF
No
after-ventilation.
After-ventilation
period of 3 minutes
3.1 Service mode
RED
No flow (C-NC).
GREEN
Flow (C-NO).
YELLOW
No signal from PDS. Check the wiring.