![Exhausto CO2B sensor-AS Manual Download Page 23](http://html1.mh-extra.com/html/exhausto/co2b-sensor-as/co2b-sensor-as_manual_2450176023.webp)
3004258_2018_01_12.fm
23/48
Example
Changing the
settings
See EXact basic instructions for changing from the default settings:
• Start: 800 ppm
• Maximum: 1200 ppm
4
After changing menu settings it is
always important to return to the
main menu to save your settings
by selecting "Save settings" in
menu 10
Using
select “Yes” and end
with
Step
Action
The display shows
10 Save settings
Save settings >
Last saved:
Date
Time
No
15.02.2011
15:30.22
4.2 Operation
CO
2
concentration in the
air is...
Airflow...
A
less than Start
is the same as set value
B
between Start and
Maximum
increases gradually to a high level, depending
on the current CO
2
level
C
greater than Maximum
is increased to maximum air replacement