The sensor must be located in a representative location in one of the ventilated rooms,
or in the extract air duct (in VEX) after the extract air filter.
Location in room
Note that the sensor cable should not be extended to more than approx. 10 m. For
positions further than 10 m away, MIOCO2 (accessory) can be used.
Position in extract
air duct in VEX
Note that there are no cable bushings.
NB
If an RHB sensor is already fitted, a CO2B sensor cannot be directly connected. In that
case, use MIOCO2 instead.
3
Location:
•
Connect the plug on the
accompanying cable to the EXact
PCB as shown on the diagram
(see p. 5)
•
Pull the other end through the
lead-in bushing and into the fan
space.
•
Pull it further through the bushing
to the space behind the exhaust
filter.
•
Connect the wires to the CO2B
sensor as shown on the diagram
(see p. )
•
Place the CO2B sensor in the
space behind the exhaust filter
•
The VEX is designed to allow the
CO2B sensor to be mounted with
two screws.
•
The connection terminal must face
upwards.
Step
Action
Illustration
RD
13110-
01
2.2 Location in other units with EXact2