1.3
Ordering Codes
The complete product ordering codes are:
Ordering Code Description
RME2-AI-100-00-80-IA3
(1) serial port RS-232
(8) 0-10V / 4-20 mA Inputs
Ethernet port 10/100 Mbps
1.4
Technical Specifications
Technical Specifications
Network Protocols
Modbus TCP, HTTP, DHCP, ICMP, ARP, SNMP
Analog Inputs
0-10V / 4-20mA (Zi = 62
Ω
)
Input Resolution
12 bits
Network port
Ethernet 10/100 Mbps, RJ45 Connector
Serial Protocols
Modbus RTU/ASCII for Gateway mode
Serial Port
(1) RS-232 with plug-in terminals
Administrator
HTTP Served password protected
Command Console Serial through RS-232 port
Firmware update
Through configuration web page
Indicators
Power LED
Network status LED
Data LED
Measurements
100mm x 22,5mm x 112mm (Height x Width x Length)
Power Supply
10 to 30 V
DC
Consumption
170mA @ 12V
DC
/
90 mA @ 24 V
DC
Temperatures
Operation Temperature: -15°C to 65°C
Storage Temperature: -40°C to 75°C
Warranty
1 year