Manual UVC Air Sanitizer V1000E
13.11.2020
Page
24
of
33
7. Maintenance
WARNING: Do not exchange broken or malfunctioning parts with ones that are
not accredited by the manufacturer because serious injuries and property
damage can occur.
WARNING: The maintenance must be done by qualified persons.
WARNING: Always disconnect the device from mains power while working on
the device!
WARNING: When replacing the tubes wear gloves to protect you and the
tubes. To protect your eyes, wear safety glasses or a face shield.
7.1 Life time of UVC tubes
UVC tubes have a limited life time. They are subject to a continuous aging process.
The life time of the UVC tubes is 12,000 hours under normal operating conditions
(power drop 25% ± 5% compared to the nominal UVC output of the respective UVC
source).
The effective radiation is far outside the visible range and the UVC emissions are continuously
reduced. It is therefore recommended to specify the operating conditions and the replacement
date in a maintenance plan.
Figure 8 Lifetime UVC tubes
Continuous operation increases the life time of the UVC tubes. The devices are
designed for continuous operation and should not be switched on and off often.
Frequent switching (> 3 switching operations / day) significantly accelerates the
aging process.