Configuration
15 (44)
User level
•
Read
: User can only monitor data.
•
Write
: Same as Read + user can acknowledge alarms and clear logs and
alarm history.
•
Admin
: Same as Write + access to the
Configuration
menu. Admin users
can add and change parameters, templates, devices, pages, alarms and
bindings.
•
Super Admin
: Same as Admin + access to the
Setup
menu. The Super
Admin has full access to all parts of the system.
Password
Enter a password here when adding a new user. To change the password for an
existing user: check the box
Change password
and enter a new password.
Repeat password
When adding a new password the password has to be repeated here.
3.4.2
Setup | Modbus
Fig. 23
Modbus setup page
Make sure that the Modbus devices are correctly connected to the Netbiter gateway before con-
tinuing. Each Modbus device must also be setup with a template and a unique slave address,
see
Configuration, p. 12
.
Two devices cannot have the same Modbus slave address. If this happens, the
serial bus will not be able to communicate with all slaves on the bus.
Netbiter LC300 Series User Manual
SCM-1202-047