background image

rol

Panel

CONTROL

SYSTEM

K6

K7

R6

R7

C7

+

C6

+

D11

D12

D10

D6

D4

D9

D5

D3

D21

D22

D20

D19

D24

D23

D25

D26

C

W

Y

R

ZONE

2

T'STAT

C

W

Y

R

R1

0

B

G

ZONE

1

T'STAT

CAUTION

0

R

C

+

-

ADDITIONAL

ZONE

PANEL

#1:

WIRING

DIAGRAM

HEATING

ONLY

INSTALLATION

rol

Panel

K6

K7

R6

R7

C7

+

C6

+

D11

D12

D10

D6

D4

D9

D5

D3

D21

D22

D20

D19

D24

D23

D25

D26

C

W

Y

R

ZONE

2

T'STAT

C

W

Y

R

R1

0

B

G

ZONE

1

T'STAT

CAUTION

0

R

C

+

-

ADDITIONAL

ZONE

PANEL

#2:

WIRING

DIAGRAM

COOLING

ONLY

INSTALLATION

AP PL ICA TIO N

NO TES

OPERATION

To operate the system in the heat mode,
the "B" terminal has to be made to the "R1"
terminal on the zone 1 terminal block.

This

allows any zone thermostat to call for heat.
When a zone calls for heat, the control
panel closes

the circuit

from "R" to "W"

activating   the   furnace.

The   zone   damper

calling for heat remains open and zones
satisfied will close. The fan and limit control
in the furnace will operate the fan.

1.

HEAT

MODE:

2.

COOL

MODE:

To operate the system in the cool mode,
the "O" terminal has to be made to the "R1"
terminal on the zone 1 terminal block.

This

allows for any thermostat to call for cooling.
On call for cooling, terminals "R", "G" and
"Y" are made

to

bring

on

the fan and

compressor.

The dampers for zones calling

will remain open; the dampers satisfied will
close.

3.

OFF POSITION:

When the subbase on zone 1 is in the
"OFF" position the entire system is disabled.

4.

CONTINUOUS

FAN:

When

placing

the

fan

switch

on

the

subbase from "AUTO" to "ON" position, the
panel closes the circuit between "R" and "G"
terminals to energize the fan relay.

5.

OPEN-CLOSE SWITCHES:

If left in the open position when all zones
satisfy,

the

damper

will

drive

to

open

position.

If left in closed position, when all

zones

satisfy

,

the

damper

will

remain

closed unless it is the last zone to satisfy;
then it will remain open.

NOTE: The last zone to satisfy will always
be open regardless of position of switch.

WIRING

1.

HVAC SYSTEM:

Wiring the HVAC system to the EWC-ST-2E
or EWC-ST-3E is typical of wiring a subbase
to

a

heating/cooling

system.

(4

wires

required.)

The following terminals are on the system
terminal block:

R-

Y-

W-

G-

Wire

to

the

RH

heating

transformer

and/or the RC cooling transformer.

Wire to the Compressor Relay.

Wire

to

Heat

Control

(gas

valve,

oil

burner relay) on system terminal block.

Wire to Fan Relay.

2.

TRANSFORMER 24V 40VA:

A separate 24V 40VA transformer is required
to be wired to terminals 1 and 2 of the
terminal block labeled "T-Former".

(2 wires

required.) This transformer powers the panel
board, thermostats and damper motors.

It

does

not

power

the

furnace

or

the

air

conditioner.

The board is now protected by 

a

 Thermal Polyfuse

 at the transformer input.

When the polyfuse trips it will get quite hot. To 
reset the breaker, remove the 24 VAC for 
approximately 30 seconds. Check the damper 
motors and field wiring for shorts. If adding two 
panels together, be sure of wiring in (+ and - ) 
circuit.

3.

ZONE DAMPER MOTORS:

Use 3 conductor wire from each set of MAN
or

RDN

zone

damper

terminals

or

2

conductor

wire on

"SR" dampers

to

the

panel. See diagrams #4 and 5 when wiring
more than one damper per zone.

ZONE 1: Thermostats that have subbases
with "B" and "O" terminals are required to
enable system changeover.

These include

mechanical

and

battery

operated

thermostats (6 wires required - terminals W,
Y, G, R, B and O), and electro-mechanical
and programmable

digital thermostats (24

VAC, 7 wires required - terminals C, W, Y,
G, R, B and O).

If model MCS-DXB remote selector switch is
used, it will be wired to the zone 1 terminal
block in place of the changeover subbase
(7 wires required total: 4 on the MCS-DXB -
B, G, O and R1; 3 on the thermostat - W,
Y and R). See diagram #3.

OTHER ZONES: 3 wires are required for
mechanical

and

battery

operated

thermostats - terminals W, Y and R. 4 wires
are required for electro-mechanical and 24
VAC digital thermostats - terminals C, W, Y
and R. No subbases required.

See

page

6

for

specific

types

of

thermostats required.

4.

THERMOSTATS:

5.

HEAT

ONLY OR

COOL

ONLY

Zone 1 no longer requires a subbase or
remote switch.

All zones need only a two

or three wire thermostat to operate in either
heat or cool.

APPLICATIONS:

2

CONTROL

SYSTEM

EWC Controls Inc.

385 Highway 33

Englishtown, NJ

07726 •

800-446-3110

FAX 732-446-5362

R

G

Y

W

O

B

ZONE 2 THERMOSTAT

R

G

Y

W

O

B

ZONE 1 THERMOSTAT

FIELD

INSTALLED

JUMPER

R

G

Y

W

O

B

ZONE 2 THERMOSTAT

R

G

Y

W

O

B

ZONE 1 THERMOSTAT

FIELD

INSTALLED

JUMPER

Summary of Contents for ULTRA-ZONE ST2E Series

Page 1: ...as blown The Polyfuse protects the panel against shorts in the thermostat or damper field wiring It does not protect against shorts in the H VA C e q u i p m e n t f i e l d w i r i n g S e e pa g e 2 The location of the J1 jumper on the panel has also changed and there is now an arrow pointing to it The J1 jumper enables fan operation in Heat mode as well as Cooling mode With the exception of the...

Page 2: ...R Y W G Wire to the RH heating transformer and or the RC cooling transformer Wire to the Compressor Relay Wire to Heat Control gas valve oil burner relay on system terminal block Wire to Fan Relay 2 TRANSFORMER 24V 40VA A separate 24V 40VA transformer is required to be wired to terminals 1 and 2 of the terminal block labeled T Former 2 wires required This transformer powers the panel board thermos...

Page 3: ...TYPE DAMPERS EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3110 FAX 732 446 5362 CB1 RED RED BROWN ORANGE GREEN 1 6 4 1 6 4 1 6 4 1 6 4 24VAC TRANSFORMER 40 60VA RA TING MAX NUMBER OF 4 DAMPERS PER ZONE Multiple Damper Wiring on a Single Zone using a Separate Transformer and an Isolating Relay Maximum of 4 dampers per 40 va transformer M1 M2 M4 M6 ZONE MOTOR 4 6 1 4 6 1 4 6 1 2 1 3 ...

Page 4: ...6 ZONE1 MOTOR MOTOR Model CONTROLS Englishtown K9 K8 X R G W Y B O 1 2 K4 SW1 24V T FORMER K2 K1 K5 OPEN CLOSE OPEN CLOSE SW2 M1 M2 M4 M6 ZONE2 M1 M2 M4 M6 ZONE1 MOTOR MOTOR Model CONTROLS Englishtown K9 K8 X R G W Y B O 1 2 K4 SW1 24V T FORMER K2 K1 K5 OPEN CLOSE OPEN CLOSE SW2 M1 M2 M4 M6 ZONE2 M1 M2 M4 M6 ZONE1 MOTOR MOTOR Model CONTROLS Englishtown EWC Controls Inc 385 Highway 33 Englishtown N...

Page 5: ...tion procedures ADDITIONAL ZONE PANEL EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3110 FAX 732 446 5362 CB1 K9 K8 C9 C8 Z9 Z8 D19 D20 D21 D22 D26 D25 D24 D23 Z7 C6 C7 D12 D11 D10 D9 D3 D4 D5 D6 Z6 K5 K4 K2 K1 K6 K7 C2 C1 C5 C4 Z5 Z4 Z2 Z1 D8 D7 D1 D2 SW2 SW1 C C R R W W Y Y ZONE 2 ZONE 1 OPEN OPEN CLOSE CLOSE M1 M1 M2 M2 M4 M4 M6 M6 ZONE2 ZONE1 T STAT T STAT MOTOR MOTOR R O C G B ...

Page 6: ...ANUFACTURER DIGITAL NON PROGRAMMABLE THERMOSTATS Battery Operated DIGITAL PROGRAMMABLE THERMOSTATS Battery Operated EWT 725 Not Available Not Available EWC CONTROLS EMERSON HONEYWELL Not Available Not Available EWT 601 2 ZONES 2 HIGHER 3 WIRES REQUIRED DIGITAL NON PROGRAMMABLE THERMOSTATS Battery Operated DIGITAL PROGRAMMABLE THERMOSTATS Battery Operated EWT 725 EWC CONTROLS EMERSON HONEYWELL Not ...

Page 7: ...end on position of OPEN CLOSED switch In OPEN position damper will drive to open position In CLOSED position all voltage is removed from damper motor motor will remain in whatever position it was in when all thermostats satisfied If 24 volts is present from M1 to M4 and M1 to M6 damper motor may either be turning or stuck between open and closed postions EWC Controls Inc 385 Highway 33 Englishtown...

Page 8: ...Z1 Z3 D8 D7 D1 D2 SW2 SW1 Y W R C ZONE 3 C C R R W W Y Y ZONE 2 ZONE 1 OPEN OPEN CLOSE CLOSE OPEN CLOSE M1 M2 M4 M6 ZONE3 M1 M1 M2 M2 M4 M4 M6 M6 ZONE2 ZONE1 T STAT T STAT T STAT MOTOR MOTOR MOTOR R O C G B O R1 X R G W Y B O 1 2 24V T FORMER Model EWC ST 3E CONTROL SYSTEM CONTROLS INC Englishtown NJ CAUTION ADDITIONAL ZONE PANEL CB1 732 446 5362 1 6 4 DAMPER MOTORS 1 6 4 1 6 4 24VAC TRANSFORMER C...

Reviews: