6. WATER SUPPLY - Required Criteria

9. WIRING THE STEAM HUMIDIFIER

7.   M OUNTING  THE  STEAM  HUMIDIFIER

8. STEAM OPERATION - Required Criteria

A. WATER SUPPLY USING THE SADDLE VALVE
    FURNISHED WITH UNIT.  Important! See page 14.

A.  INSTALLING AND WIRING THE HUMIDISTAT

B. OVERFLOW & DRAIN LINES - Required Criteria

Installation instructions for the saddle valve are printed on the 
plastic bag containing the saddle valve and its components. 
Tap  into  a  1/2”  or  3/4”  domestic  cold  water  line.  Avoid 
connecting to water lines from a Reverse Osmosis system or 
De-ionized  water  systems. 

The  supply  water  must  read  a 

minimum of 25 ppm in order for the Steam unit to reliably 
sense the water. 

NOTE

: Never install the saddle valve on the bottom of the 

water pipe. Sediment in the water pipe may clog the saddle 
valve. 

Flush the line before connecting to the unit.

 

tightening  the  hex  compression  nut,  tighten  only  enough  to 
assure there are no leaks.

NOTE

: Saddle valves do not meet plumbing codes in some 

areas. A “T” fitting with a valve may be required to meet code 
or, if low water pressure causes frequent water alerts on the 
steam humidifier. 

NOTE: Flush the new water line before 

connecting it.

NOTE:

 The use of City water or Municipal water is preferred. 

Softened water is preferred over untreated well water. 

Specify 

the  Optional WFA-195  disposable  water  filter  for  treating 
any water supply that is very high in mineral content.
NOTE: 

Use  a  water  hammer  arrester  (WH-100)  if  water 

spikes occur (pipes bang)during fill ups.

When 

A temperature sensor is mounted in the water reservoir of the 
humidifier.  As  the  water  temperature  increases  to  about  170 
degrees F, the computer closes a set of blower relay contacts to 
start the system fan. When the water cools to about 140 degrees 
F, the  computer will open the relay contacts to shut off the fan. 
This operational sequence drastically decreases the chances of 
condensation occurring inside the duct-work.

A humidistat, such as the Model #072000 is required to control 
the Steam Humidifier. The humidistat may be installed on the 
wall  in  the  living  space  or  on  the  return  air  duct.

  NOTE: 

Continuos fan operation should be initiated if the humidistat is 
installed on the return air duct!

 Instructions for installation are 

packaged  with  each  humidistat.  Follow  wiring  instructions 
carefully!

DO NOT

 connect any foreign voltage to the “H” terminals of the 

humidifier!

 The Humidifier   supplies it’s own control voltage. 

Simply connect the two “H” terminals straight to any dry contact 
humidistat terminals.

 If you are using a 3rd party Humidistat 

that has powered terminals, you must use an isolating relay 
to operate the Steam Humidifier. Failure to do so will result 
in circuit board failure  and will  void all  warranties.

Schematics  on  the  following  pages  describe  the  suggested 
interlock  wiring  arrangement  for  different  HVAC  systems. 
Interlocking may be performed on systems that provide a 24vac 
NEC Class 2 terminal block for system control.

AIR  PROVING  FEATURE: 

The  Steam  Humidifier  has  an 

integrated air proving feature that allows the user to install a sail 
switch  and/or  high  humidity  switch  in  the  duct  and  easily 
achieve  fail  safe  shutdown  in  the  event  of  fan/blower  failure. 
This  feature  prevents  the  Steam  Humidifier  from  operating 
unless adequate airflow is proven thereby avoiding a saturated 
duct condition. 

WARNING: It is highly recommended to use 

an  airflow  proving  device.  In  particular  Duct-Board 
applications should always use an airflow proving device.  

A factory jumper wire is provided and must be removed when 
connecting  the  sail  switch  or  other  field  supplied  air  flow 
proving device. Leave the jumper in place if you decide not to 
use the airflow proving feature. 

IMPORTANT NOTE: If the Steam Humidifier is removed 
and  disconnected  from  the  system,  the  blower  interlock 
circuit must be restored to it's original configuration. Failure 
to do so may result in loss of blower operation during cooling 
modes!

Use gasket material to seal 

where the front plate or tank flange 

contacts the duct-work. Place the humidifier reservoir into the 
opening  in  the  duct  and  secure  with  eight  (8)  sheet  metal 
screws. 

NOTE: If the duct-work will not support the unit in a level 
position with the water pan full of water, the duct-work 
must  be  reinforced.  Both  steam  models  weigh 
approximately  9  Lbs.  empty  and  approximately  15  Lbs. 
when full of water.

Because of the high output of this Humidifier, it must not be 
operated  without  the  blower  operating.  The  steam 
humidifier  is  designed  to  be  "Dominant"  over  the  HVAC 
System Blower. The "System" Blower will be operated by the 
humidifier  when  the  water  tank  temperature  reaches  170 
degrees F.

 A minimum of 800 cfm @ 800-900 fpm is required for 

proper operation of the steam humidifier. Lower velocities may 
result in excessive condensation inside the duct. See 

Air Proving 

Feature

 on the next column! See 

Variable Speed

 on Page 7.

The use of an overflow line and drain line is always required.

Use the supplied 1/2” ID high temperature hose. Slip the hose 
over the 1/2” OD “T” drain fitting and use a hose clamp to 
secure.

 Route the hose to a suitable drain, avoiding kinks, 

traps and sharp objects. DO NOT route the hose above the 
humidifier.  Failure to install all necessary drain lines may 
result in water leaks during normal operating conditions, 
and voids all warranties.

3

B.  FIELD WIRING

IMPORTANT:

  Dedicated  fused  circuits  and  outlets  of  the 

proper voltage and current ratings must be provided. 

Use a 

NEMA  5-20R  receptacle  for  the  S2000  and  a  NEMA  6-15R 
receptacle for the S2020.

 All wiring must conform to local and 

national codes. Failure to do so will void all warranties. 

DO NOT cut off the grounded plug and/or hard wire this unit to 
line voltage!  DO NOT use extension cords to operate this unit! 
Doing so will void all warranties.

When routing the S2000 drain hose into a condensate pump, 
be sure to cut the end of the hose at a sharp angle to prevent 
the hose from bottoming out in the pan. It could result in 
poor draining or no draining at all. Failure to do so may 
result in water backing up into the S2000 reservoir and 
eventual overflow. 

See Figure 5.

CORRECT

INCORRECT

X

CONDENSATE
PUMP

DRAIN

HOSE

FIG. 5

Summary of Contents for Ultra-Zone S2000

Page 1: ...nal parts recommended 1 Water Hammer Arrester WH 100 2 Anode Z100 3 Decorative Under Duct Cover SC100 4 Gasket Material to seal flanges field provided 5 Model APD Current Sensing Switch Sail Switch or other Airflow Proving Device 6 WFA 195 Water Filter Assembly Installation Instructions Owner s Manual WATER INLET WATER LEVEL PROBE HEATER TEMPERATURE PROBE FIG 1 Fo r Re pla ce me nt Pa rts Ca ll 80...

Page 2: ... be met you should install the unit under theductby meansof thetankflange Seepage6 If a suitable means of gravity draining the unit is not available or cannot be provided the unit will work with the drain valve electrically disconnected Call the Technical Support Hotline for Instructions It is highly recommended but not required that the use of Fiberglass duct board with this product includesan an...

Page 3: ...difier has an integrated air proving feature that allows the user to install a sail switch and or high humidity switch in the duct and easily achieve fail safe shutdown in the event of fan blower failure This feature prevents the Steam Humidifier from operating unless adequate airflow is proven thereby avoiding a saturated duct condition WARNING It is highly recommended to use an airflow proving d...

Page 4: ...uld read infinity no continuity when the fan blower is off 2 Turn on the fan blower at the thermostat and test for continuity across the normally open contacts with the fan blower running You should now read continuity a complete circuit when the fan blower is running 062000 Humidistat G1 R G2 H H A A S2000 S2020 Humidifier Low Voltage Terminal Block Disconnect the wires from the A terminals and c...

Page 5: ...fier will obstruct approximately 70 square inches of duct area The tank flange is no longer a factor At 92 8 square inches the smallest duct plenum that can accommodate the Steam Humidifier mounted internally would be approximately 20 by 19 20x19 380 square inches multiplied by 25 95 square inches Steam Humidifier square inches of obstruction 92 8 square inches Up flow configuration 25 percent of ...

Page 6: ... 7 7 2 6 C O N T R O L S I N C U L C U S L I S T E D 1 4 1 V P O W E R D R A I N F I L L H E A T E R B L O W E R T h e r m i s t o r H e a t e r W a t e r S u i t a b l e f o r R e s i d e n t i a l U s e O n l y M o d e l S 2 0 2 0 S t e a m H u m i d i f i e r 2 0 K W 2 4 0 V o l t 8 3 A m p s F o r R e p l a c e m e n t P a r t s C a l l 8 0 0 4 4 6 3 1 1 0 0 9 0 2 1 A 0 1 1 8 U S P A T E N T N...

Page 7: ...ocationis theonlysolution Installation instructions for the 072000 model Humidistat arepackaged with the 072000 Your humidifier may include Model 062000 Humidistat Installation instructions for the 062000 model are packaged withthe062000 There are many ways to wire and control a humidifier Refer tothewiringdiagramsonpages4and7 10 SETTINGTHEHUMIDISTAT RH OD RH TEMP MAN AUTO MODE Outside Dry Bulb Te...

Page 8: ...or the water to heat to 170 deg F If the humidistat remains closed the HEATER and BLOWER LED s will both be illuminated at the same timeandthe POWER LEDwillbeblinkingslowly E The FILL LED will illuminate and the water reservoir will refill at irregular intervals depending on the boil off rate The HEATER LED should remain illuminated unless the humidistat opens or the humidifierentersadraincycleorf...

Page 9: ...he water line and the drain lines Store the unit in this condition for the summer orcontinuetothenextstep START UP Turn on the water supply Inspect the water connections and drainfittingsforleaks Plug in the S2000 power cord to the 120 VAC 240 VAC for S2020 groundedoutlet DO NOTuseanextensioncord 1 The green POWER light should blink rapidly until it detectsademandtohumidify thenitwillblinkslowly 2...

Page 10: ...hedrainvalveisunpluggedor defective 7 Debris iscloggingthedrainvalveordrainline 8 Reset the unit by unplugging the power cord and re connecting Both Red ServiceLights error 3 areon constantly HEATER FAILURE This is an indication that the water temperature is not increasing or reaching the boiling point 1 Faultyheaterelementorfaultywireconnection 2 This can happen if the unit is operated without wa...

Page 11: ... 100 Z 100 2004 2006 2120 2001 2240 2002 2008 2005 2006 2003 2007 2001 1 2 3 4 5 6 7 8 9 10 DESCRIPTION OF PART S2000 S2020 PART NO PART NO 11 2009 2009 UNDER DUCTSTEAM COVER not shown Fo r Re pla ce men t Pa rts Ca ll 800 44 6 31 10 09 02 1A 01 18 U S PATENT NUMBER 57 58 01 8 se ria l nu mbe r Ewc 385 Highway 33 Englishtown NJ 07726 CONTROLS INC U L C US LISTE D 14 1V POWER DRAIN FILL HEATER BLOW...

Page 12: ...m e mail info ewccontrols com Tel 800 446 3110 Fax 732 446 5362 Figure 18 12 DRAIN COCK VALVE T ADAPTER 1 4 NPT OVERFLOW TUBE 50 ID x 6 LG BARBED TEE 1 4 18 NPT TO JUMPER WIRE 20GA X 1 50 LONG MOLEX PLUG BLACK WIRES 18GA X 18 LONG SOLENOID VALVE 24 60 VAC ...

Page 13: ...nsor is not required to use the Humidistat in the basic or manual mode The 072000 operates on 24vac and has a set of isolated dry contacts for activating the humidifier Terminals are also provided for the Outdoor air Temperature Sensor Part OAS The 072000 can be installed on the return air duct or it can be installed on an interior wall within the conditioned space EWC Controls recommends an inter...

Page 14: ... disconnected and the unit has been removed from the duct Refer to the blow up view on Page 11 Using a phillips screwdriver remove the two screws that hold the baffle plate to the tank Lift the baffle slightly back to clear the water probe and then straight up and out of the tank You can then see the round Z100 or rather what is left of it after a single season Notice the heavy scale build up on t...

Page 15: ... The SC100 is just the latest innovation in the Ultra Zone Steam Humidifier line as we continue in our pursuit of Excellence Without Compromise EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3110 FAX 732 635 8646 E Mail info ewccontrols com P N 090376A0151 REV A SC100 PART 2009 DECORATIVE COVER S2000 S2020 STEAM HUMIDIFIER Copyright 2003 EWC Controls Inc All Rights Reserved SC100Inst...

Page 16: ...e __________Service Performed ________________________________________________________ Date of Service __________Service Performed ________________________________________________________ Date of Service __________Service Performed ________________________________________________________ Date of Service __________Service Performed ________________________________________________________ Date of Se...

Reviews: