8
2551 Blind Magmeter
1
2
3
4
10K
5-24 VDC
Ground
Not used
Frequency Out
2551 Magmeter
Install a pull-up resistor when connecting the
2551 Magmeter to other manufacturer's flowmeters.
2551 Frequency Out to other manufacturer's equipment
• If connecting the 2551 Magmeter to a fl ow instrument from another
manufacturer, 5 to 24 VDC power must be provided to the 2551.
• A 10 KΩ pull-up resistor (not supplied) must also be connected
between terminals 1 and 2.
Calibration and Software Confi guration
No calibration is necessary to begin using the 2551. The application and performance settings are pre-set to meet the requirements
of most applications.
The 2551 application and performance settings can be customized using the Signet 3-0252 Confi guration Tool and software. Refer
to the Signet 3-0252 Confi gurationTool manual for details to adjust the following parameters:
• 4 to 20 mA span
: Factory setting is 0 to 5 m/s. Can be customized to any range.
• Noise Rejection Filter
: Factory set for 60 Hz. Can be changed to 50 Hz.
• Low Flow Cutoff
: Factory setting is 0.05 m/s. Can be customized to any velocity.
• Averaging Time
: Factory setting is 14 seconds. Can be customized from 0.1 seconds to 100 seconds.
• Sensitivity
: Factory setting is 25% of full scale. Can be customized to any % of full scale.
Wiring with Frequency Other Manufacturer's Equipment