18
EvoHeat Fusion-i Series Manual
7.2 Frequency Conversion Board Fault Table
Protection/Fault
Fault
Display
Reason
Elimination Methods
Drv1 MOP alarm
F01
MOP drive alarm
Recovery after the 150s
Inverter offline
F02
Frequency conversion board and main board
communication failure
Check the communication connection
IPM protection
F03
IPM modular protection
Recovery after the 150s
Comp. Driver Failure
F04
Lack of phase, step or drive hardware
damage
Check the measuring voltage check
frequency conversion board
hardware
DC Fan Fault
F05
Motor current feedback open circuit or short
circuit
Check whether current return wires
connected motor
IPM Overcurrent
F06
IPM Input current is large
Check and adjust the current
measurement
Inv. DC Overvoltage
F07
DC bus voltage>Dc bus over-voltage
protection value
Check the input voltage
measurement
Inv. DC Lessvoltage
F08
DC bus voltage<Dc bus over-voltage
protection value
Check the input voltage
measurement
Inv. Input Lessvolt.
F09
The input voltage is low, causing the input
current to be high
Check the input voltage
measurement
Inv. Input Overvolt
F10
The input voltage is too high, more than
outage protection current RMS
Check the input voltage
measurement
Inv. Sampling Volt
F11
The input voltage sampling fault
Check and adjust the current
measurement
Comm. Err DSP-PFC
F12
DSP and PFC connect fault
Check the communication connection
Input Over Cur.
F26
The equipment load is too large
PFC Fault
F27
The PFC circuit protection
Check the PFC switch tube short
circuit or not
IPM Over heating
F15
The IPM module is overheat
Check and adjust the current
measurement
Weak Magnetic Warn
F16
Compressor magnetic force is not enough
Inv. Input Out Phase
F17
The input voltage lost phase
Check and measure the voltage
adjustment
IPM Sampling Cur.
F18
IPM sampling electricity is fault
Check and adjust the current
measurement
Inv. Temp Probe Fail
F19
Sensor is short circuit or open circuit
Inspect and replace the sensor
Inverter Overheating
F20
The transducer is overheat
Check and adjust the current
measurement
Inv. Overheating Warn
F22
Transducer temperature is too high
Check and adjust the current
measurement
Comp. Overcut. Warn
F23
Compressor electricity is large
The compressor over-current
protection
Input Over Cur. Warn
F24
Input current is too large
Check and adjust the current
measurement
EEPROM Error Warn
F25
MCU error
Check whether the chip is damaged
Replace the chip
V15V over/undervoltage
fault
F28
The V15C is overload or undervoltage
Check the V15V input voltage in
range 13.5v~16.5v or not