4.3 Location of Install & Minimum Clearances 

The heat pump can be installed onto a concrete basement by using expansion screws, or onto a steel frame with 

rubber feet which can be placed on the ground or the roof. Ensure that the unit is placed horizontally. 

 

The unit can be installed in any place outdoors which will be able to support the weight of a heavy unit such as a 

terrace, roof, the ground and any other places deemed suitable. 

 

The location must have good ventilation. 

 

The location must be free from heat radiation and other fire hazards. 

 

In cold climates, a pall is needed in winter to protect the unit from snow. 

 

There must be no obstacles near the inlet and outlet of the unit. 

 

The installation location must be protected from strong winds or air. 

 

There must be a water channel around the heat pump to drain condensing water. 

 

Leave enough space around the unit for maintenance. 

 

A>500mm B>1500mm  C>1000mm  D>500mm 

4.4 Plumbing Component 

Please pay attention to the below matters when the water pipe is connected. 

 

Try to reduce the resistance to the water from the piping. 

 

The piping must be clear and free from dirt and blockage. A water leakage test must be carried out to ensure 

that there is no water leaking before the installation can be made. 

 

The pipe must be tested by pressure separately. DO NOT test it together with the unit. 

 

There must be an expansion tank on the top point of the water loop, and the water level inside the tank 

must be at least 0.5meters higher than the top point of the water loop. 

 

The flow switch is installed inside of the heat pump, check to ensure that the wiring and action of the switch 

is normal and controlled by the controller. 

 

Try to avoid any air from being trapped inside the water pipe, there must be an air vent on the top point of 

the water loop. 

 

There must be a thermometer and pressure meter at the water inlet and outlet for easy inspection during 

running. 

4.5 Electrical Component 

 

Open the front panel and open the power supply access. 

 

The power supply must go through the wire access and be connected to the power supply terminals in the 

controlling box. Then connect the 3-signal wire plugs of the wire controller and main controller. 

 

If an external water pump is required, please insert the power supply wire into the wire access and connect 

it to the water pump terminals. 

 

If an additional auxiliary heater is needed to be controlled by the heat pump controller, the relay (or power) 

of the aux-heater must be connected to the relevant output of the controller. 

 

Summary of Contents for Evo Control 17

Page 1: ......

Page 2: ...HELP Button __________________________________________________________________9 5 2 2 Starting Shutting Down ________________________________________________________________9 5 2 3 Switching Modes____...

Page 3: ...with these recommendations will invalidate the warranty This manual and all others are available for download on our website The Evo Control Series air to water heat pump is designed for multiple use...

Page 4: ...3 Evo Control 17 25 Manual 2 2 Dimensions Evo Control 17 Evo Control 25...

Page 5: ...Quantity 2 Fan Power Input W 120x2 200x2 Fan Rotate Speed RPM 850 750 Noise dB A 56 59 Hot water volume L h 57 Water Pump Input kW 0 2 0 75 Water Head m 13 5 24 Water Connection Inch 1 1 5 Water Flow...

Page 6: ...off before any work is started on the unit Do not work on the electrical components if water or high humidity is present on site When the unit is being connected ensure that no impurities are introduc...

Page 7: ...6 Evo Control 17 25 Manual 4 Installation 4 1 Application for Air Con 4 2 Application for Air Con and Super Heater for Hot Water...

Page 8: ...leakage test must be carried out to ensure that there is no water leaking before the installation can be made The pipe must be tested by pressure separately DO NOT test it together with the unit There...

Page 9: ...nts and that they are in good order When powering the unit on review the indicator on the controller to see if there is any indication of failure The gas gauge can be connected to the check valve to s...

Page 10: ...clock or turn the timer on off UP Press this key to select the upwards option or increase the parameter value DOWN Press this key to select the downwards option or decrease the parameter value 5 2 Fun...

Page 11: ...re At the main interface press the UP or DOWN key to adjust the temperature setting as desired Once complete press the button to save the settings and exit Press the ON OFF button to exit without savi...

Page 12: ...ss to enter the timer setting interface The process is much the same as adjusting the Clock settings To cancel and return to the previous menu press the ON OFF button 5 2 7 1 Timer Each timer has an O...

Page 13: ...ere 8am 10am Timer 3 were 1pm 5pm the unit would operate or stop accordingly 5 2 8 Keyboard Lock To lock the controller after adjusting settings at the main interface hold the ON OFF button for 5 seco...

Page 14: ...oken Check the pressure switch and cold circuit Low pressure 2 protection E22 12 on 1 off The low pressure switch is broken Check the pressure switch and cold circuit Heat source side water flow failu...

Page 15: ...the temp sensor System 1 2 3 4 high Pressure protection E11 system1 E21 system2 E31 system3 E41 system4 The high pressure switch is broken Check the pressure switch and cold circuit System 1 2 3 4 lo...

Page 16: ...recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor does not run Power supply failure Chec...

Page 17: ...illed water Installation Requests 1 The Factory only offers main unit in the legend the other modules which are indispensable fittings are to be provided by the user or installation company 2 The unit...

Page 18: ...ndle A can return close when the system is full of water 5 Automatic filled water valve needs cleaning in a periodic time and then you must close the tap unscrew the plug D and remove the inside filte...

Page 19: ...o the electronic boiler or warm net pipe for city accordingly 1 Water chiller and heat pump assistant gas fired boiler 2 Water chiller and heat pump assistant electronic boiler 7 5 Unit Parameters Mea...

Page 20: ...e input 10 RO 08 Spray valve output 220VAC 31 AI 05 Ambient temperature input 11 RO 09 Alarm system output 220VAC 32 AI 06 System 1 antifreeze temperature input 12 DI DO 1 Mode indicator output 33 AI...

Page 21: ...put 12 RO 10 Spray valve output 220VAC 38 AI 11 System 4 antifreeze temperature input 13 RO 11 Alarm system output 220VAC 39 AI 12 System 1 suction temperature input 14 DI DO 1 Emergency switch output...

Page 22: ...23 148A 2 x 50mm2 50mm2 225A 148 186A 2 x 70mm2 70mm2 250A 186 224A 2 x 95mm2 95mm2 280A Three Phase Unit Nameplate maximum current Phase Line Earth Line MCB Creepage Protector Signal Line No more tha...

Page 23: ...it is restarted Please drain out the water in the super heater of the heat pump unit in winter when the super heater is not used The water loop of the heat pump MUST be protected from freezing in wint...

Page 24: ...or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your re...