evoheat Evo Control 17 Installation & Operation Manual Download Page 16

 

 

15 

Evo Control 17 & 25 Manual 

6.3 System Failures (Both Models) 

FAILURE 

POSSIBLE CAUSES 

SOLUTIONS 

Heat pump cannot be 

started 

Wrong power supply 

Shut off the power and check power supply 

Power supply cable loose  

Check power cable and correct the connection  

Circuit breaker open 

Check for the cause and replace the fuse or circuit 

breaker 

Water pump is running 

with high 

Noise or without water 

Lack of water in the piping 

Check the water supply and charge water to the piping 

Too much air in the water loop 

Discharge the air in the water loop 

Water valves closed 

Open the valves in water loop 

Dirt and block on the water filter 

Clean the water filter 

Heat pump capacity is 

low, compressor does not 

stop 

Lack of refrigerant 

 

Check for the gas leakage and Recharge the Refrigerant 

Bad insulation on water pipe 

Make good insulation on water pipe 

Low heat exchange rate on air 

Side exchanger 

Clean the air side heat exchanger 

 

Lack of water flow 

Clean the water filter 

High compressor exhaust 

Too much refrigerant 

Discharge the redundant gas 

Low heat exchange rate on air side 

exchanger 

Clean the air side heat exchanger 

Low pressure problem of 

the system 

Lack of gas 

Check the gas leakage and recharge freon 

Block on filter or capillary 

Replace filter or capillary 

Lack of water flow 

Clean the water filter and discharge the air in water loop 

Compressor does not run 

Power supply failure 

Check off the power supply 

Compressor contactor broken 

Replace compressor contactor 

Power cable loose 

Tighten the power cable 

Protection on compressor 

Check the compressor exhaust temp. 

Wrong setting on return water 

Temp. 

Reset the return water temp 

Lack of water flow 

Clean the water filter and discharge the air in water loop 

High noise of compressor 

Liquid refrigerant goes into 

Compressor 

Bad evaporation check the cause for bad evaporation 

and get rid of it 

Compressor failure 

Use new compressor 

Fan does not run 

Failure on fan relay 

Replace the fan relay 

Fan motor broken 

Replace fan motor 

The compressor runs but 

heat 

Pump has no heating or 

cooling capacity 

No gas in the heat pump 

 

Check system leakage and recharge refrigerant 

 

Heat exchanger broken 

Find out the cause and replace the heat exchanger 

Compressor failure. 

Replace compressor 

Low outlet water 

temperature 

Low water flow rate 

 

Clean the water filter and discharge the air in water loop 

Low setting for the desired water 

temp 

Reset the desired water temperature 

Low water flow 

protection 

Lack of water in the system 

 

Clean the water filter and discharge the air in water loop 

Failure on flow switch 

Replace the flow switch 

 

 

 

 

 

Summary of Contents for Evo Control 17

Page 1: ......

Page 2: ...HELP Button __________________________________________________________________9 5 2 2 Starting Shutting Down ________________________________________________________________9 5 2 3 Switching Modes____...

Page 3: ...with these recommendations will invalidate the warranty This manual and all others are available for download on our website The Evo Control Series air to water heat pump is designed for multiple use...

Page 4: ...3 Evo Control 17 25 Manual 2 2 Dimensions Evo Control 17 Evo Control 25...

Page 5: ...Quantity 2 Fan Power Input W 120x2 200x2 Fan Rotate Speed RPM 850 750 Noise dB A 56 59 Hot water volume L h 57 Water Pump Input kW 0 2 0 75 Water Head m 13 5 24 Water Connection Inch 1 1 5 Water Flow...

Page 6: ...off before any work is started on the unit Do not work on the electrical components if water or high humidity is present on site When the unit is being connected ensure that no impurities are introduc...

Page 7: ...6 Evo Control 17 25 Manual 4 Installation 4 1 Application for Air Con 4 2 Application for Air Con and Super Heater for Hot Water...

Page 8: ...leakage test must be carried out to ensure that there is no water leaking before the installation can be made The pipe must be tested by pressure separately DO NOT test it together with the unit There...

Page 9: ...nts and that they are in good order When powering the unit on review the indicator on the controller to see if there is any indication of failure The gas gauge can be connected to the check valve to s...

Page 10: ...clock or turn the timer on off UP Press this key to select the upwards option or increase the parameter value DOWN Press this key to select the downwards option or decrease the parameter value 5 2 Fun...

Page 11: ...re At the main interface press the UP or DOWN key to adjust the temperature setting as desired Once complete press the button to save the settings and exit Press the ON OFF button to exit without savi...

Page 12: ...ss to enter the timer setting interface The process is much the same as adjusting the Clock settings To cancel and return to the previous menu press the ON OFF button 5 2 7 1 Timer Each timer has an O...

Page 13: ...ere 8am 10am Timer 3 were 1pm 5pm the unit would operate or stop accordingly 5 2 8 Keyboard Lock To lock the controller after adjusting settings at the main interface hold the ON OFF button for 5 seco...

Page 14: ...oken Check the pressure switch and cold circuit Low pressure 2 protection E22 12 on 1 off The low pressure switch is broken Check the pressure switch and cold circuit Heat source side water flow failu...

Page 15: ...the temp sensor System 1 2 3 4 high Pressure protection E11 system1 E21 system2 E31 system3 E41 system4 The high pressure switch is broken Check the pressure switch and cold circuit System 1 2 3 4 lo...

Page 16: ...recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor does not run Power supply failure Chec...

Page 17: ...illed water Installation Requests 1 The Factory only offers main unit in the legend the other modules which are indispensable fittings are to be provided by the user or installation company 2 The unit...

Page 18: ...ndle A can return close when the system is full of water 5 Automatic filled water valve needs cleaning in a periodic time and then you must close the tap unscrew the plug D and remove the inside filte...

Page 19: ...o the electronic boiler or warm net pipe for city accordingly 1 Water chiller and heat pump assistant gas fired boiler 2 Water chiller and heat pump assistant electronic boiler 7 5 Unit Parameters Mea...

Page 20: ...e input 10 RO 08 Spray valve output 220VAC 31 AI 05 Ambient temperature input 11 RO 09 Alarm system output 220VAC 32 AI 06 System 1 antifreeze temperature input 12 DI DO 1 Mode indicator output 33 AI...

Page 21: ...put 12 RO 10 Spray valve output 220VAC 38 AI 11 System 4 antifreeze temperature input 13 RO 11 Alarm system output 220VAC 39 AI 12 System 1 suction temperature input 14 DI DO 1 Emergency switch output...

Page 22: ...23 148A 2 x 50mm2 50mm2 225A 148 186A 2 x 70mm2 70mm2 250A 186 224A 2 x 95mm2 95mm2 280A Three Phase Unit Nameplate maximum current Phase Line Earth Line MCB Creepage Protector Signal Line No more tha...

Page 23: ...it is restarted Please drain out the water in the super heater of the heat pump unit in winter when the super heater is not used The water loop of the heat pump MUST be protected from freezing in wint...

Page 24: ...or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your re...

Reviews: