4
Evo Control 17 & 25 Manual
2.3 Technical Data
Evo Control 17
Evo Control 25
Cooling Capacity
kW
13.5
19.5
Btu/h
46000
67000
Heating Capacity
kW
17.0
25.0
Btu/h
58000
85000
Cooling Power Input
kW
4.7
7.0
Heating Power Input
kW
4.1
6.0
Running Current (Cooling/Heating)
A
20.4/17.8
12.1/10.3
Power Supply
230V~/50Hz
400V/3N~/50Hz
Compressor Quantity
2
3
Compressor
Rotary
Fan Quantity
2
Fan Power Input
W
120x2
200x2
Fan Rotate Speed
RPM
850
750
Noise
dB(A)
56
59
Hot water volume
L/h
57
Water Pump Input
kW
0.2
0.75
Water Head
m
13.5
24
Water Connection
Inch
1
1.5
Water Flow Volume
m
3
/h
2.8
3.8
Water Pressure Drop
kPa
34
36
Unit Net Dimensions (L/W/H)
mm
See unit drawing
Unit Shipping Dimensions
mm
See package label
Net Weight
kg
See nameplate label
Shipping Weight
kg
See package label
Cooling: Ambient temperature 35°C / 24°C, inter/outlet water temperature: 12°C / 7°C
Heating: Ambient temperature 7°C / 6°C, inter/outlet water temperature: 30°C / 35°C