Evo Control 17 & 25 Manual
7.7 Cable Specifications
Single Phase Unit
Nameplate maximum
current
Phase Line
Earth Line
MCB
Creepage Protector
Signal Line
No more than 10A
2 x 1.5mm
2
1.5mm
2
20A
30mA less than 0.1 sec
n x 0.5mm
2
10 ~ 16A
2 x 2.5mm
2
2.5mm
2
32A
16 ~ 25A
2 x 4mm
2
4mm
2
40A
25 ~ 32A
2 x 6mm
2
6mm
2
40A
32 ~ 40A
2 x 10mm
2
10mm
2
63A
40 ~ 63A
2 x 16mm
2
16mm
2
80A
63 ~ 75A
2 x 25mm
2
25mm
2
100A
75 ~ 101A
2 x 25mm
2
25mm
2
125A
101 ~ 123A
2 x 35mm
2
35mm
2
160A
123 ~ 148A
2 x 50mm
2
50mm
2
225A
148 ~ 186A
2 x 70mm
2
70mm
2
250A
186 ~ 224A
2 x 95mm
2
95mm
2
280A
Three Phase Unit
Nameplate maximum
current
Phase Line
Earth Line
MCB
Creepage Protector
Signal Line
No more than 10A
3 x 1.5mm
2
1.5mm
2
20A
30mA less than 0.1 sec
n x 0.5mm
2
10 ~ 16A
3 x 2.5mm
2
2.5mm
2
32A
16 ~ 25A
3 x 4mm
2
4mm
2
40A
25 ~ 32A
3 x 6mm
2
6mm
2
40A
32 ~ 40A
3 x 10mm
2
10mm
2
63A
40 ~ 63A
3 x 16mm
2
16mm
2
80A
63 ~ 75A
3 x 25mm
2
25mm
2
100A
75 ~ 101A
3 x 25mm
2
25mm
2
125A
101 ~ 123A
3 x 35mm
2
35mm
2
160A
123 ~ 148A
3 x 50mm
2
50mm
2
225A
148 ~ 186A
3 x 70mm
2
70mm
2
250A
186 ~ 224A
3 x 95mm
2
95mm
2
280A
If the unit is to be installed outdoors, ensure a UV resistant cable is used.