E2648 series Modbus holding registers (part 2)

Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR

RW

Description

Supported values (dec)

Default

0x00A2

162

RW

Zero adjustment for temperature
data, °C × 100

-32000...+32000 (-320,00...+320,00 °C)

0

0x00A5

165

RW

Zero adjustment for gas data, ADC

-32000...+32000 ADC units

0

0x00A6

1667

RW

Slope adjustment for gas data

1...65535

512

0x00A7

167

RW

Change rate limit for gas data,
gas unit / s

1...32000, 0 - no limit

0

0x00A8

168

RW

Integrating filter time constant, s

1...32000 (seconds), 0 - no filter

0

0x00C9

201

RW

Parameter tied to analog output 1

0-none
1- temperature
2- gas concentration
9- forced Modbus control, value set in MHR / 40204

2

0x00CA

202

RW

Parameter tied to analog output 2

0-none
1- temperature
2- gas concentration
9- forced Modbus control, value set in MHR / 40205

2

0x00CB

203

RW

Forced value for analog output 1***

0...1000 (0,0%...100,0% of output scale)

0

0x00CC

204

RW

Forced value for analog output 2***

0...1000 (0,0%...100,0% of output scale)

0

0x00D3

211

RW

Parameter tied to relay RE1

0-none
1- temperature
2- gas concentration
9- control by Modbus control, state set in MHR / 40214

2

0x00D4

212

RW

Parameter tied to relay RE2

0-none
1- temperature
2- gas concentration
9- control by Modbus control, state set in MHR / 40215

2

0x00D5

213

RW

Forced state for relay RE1***

0- off, 1 - on

0

0x00D6

214/

RW

Forced state for relay RE2***

0- off, 1 - on

0

0x00D7

215

RW

Switching delay for relay RE1

0...1000 (s)

0

0x00D8

216

RW

Switching delay for relay RE2

0...1000 (s)

0

0x00D9

217

RW

Minimal on/off time for relay RE1

0...1000 (s)

0

0x00DA

218

RW

Minimal on/off time for relay RE2

0...1000 (s)

0

* - The new value is applied after restart.
** - Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the
only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.
*** - This value is dynamic and not kept in EEPROM after restart