E2648 series Modbus holding registers (part 3)

Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR

RW

Description

Supported values (dec)

Default

0x00DB

219

RW

Control logic for relay RE1

0- none
1- relay on at high values
2- relay on at low values
3- relay on at values within the range
4- relay on for the values outside the range

0

0x00DC

220

RW

Control logic for relay RE2

0- none
1- relay on at high values
2- relay on at low values
3- relay on at values within the range
4- relay on for the values outside the range

0

0x00DD

221

RW

LOW setpoint for relay RE1

0...65535 (gas units)

see

Specifications

0x00DE

222

RW

HIGH setpoint for relay RE1

0...65535 (gas units)

see

Specifications

0x00DF

223

RW

LOW setpoint for relay RE2

0...65535 (gas units)

see

Specifications

0x00E0

224

RW

HIGH setpoint for relay RE2

0...65535 (gas units)

see

Specifications

0x00FF

255

RW

Sensor, analog outputs, LED and buzzer
status

bit[0]=0/1 - sensor present/absent, read-only!
bit[1]=0/1 - analog outputs deactivated/activated,
bit[2]= 0/1 - in case the sensor is absent, turn signaling off/on analog output1,
bit[3]=0/1 - in case the sensor is absent, turn on signaling with low current/high current
on analog output1; if bit[2]==0 this bit will be ignored,
bit[4]=0/1 - in case of sensor absent, turn signaling off/on analog output2
bit[5]=0/1 - in case of sensor absent, turn on signaling with low current/high current on
analog output2; if bit[4]==0 this bit will be ignored,
bit[6]=0/1 - current/voltage output detected on output1, read-only!
bit[7]=0/1 - current/voltage output detected on output2, read-only!
bit[8]=0/1 - LED deactivated/activated,
bit[9]=0/1 - buzzer deactivated/activated
bit[10]=0/1 - LED is on/off in normal condition
bit[11]=0/1 - LED and buzzer syncing off/on with RE1
bit[12]=0/1 - LED and buzzer syncing off/on with RE2

user defined

0x0100

256

R

Raw temperature data, °C×100

signed integer, -4000...+8500 (-40,00...+85,00 °C)

0x0101

257

R

Raw gas sensor data

ADC data 0...4095

0x0102

258

R

Measured temperature, °C×100

signed integer, -4000...+12500 (-40,00...+125,00 °C)

0x0103

259

R

Gas concentration, gas units

signed integer, -32000...+32000 (gas units)

0x0105

261

RW

0% value for analog output 1

signed integer, -32000...+32000 (ppm / ‰)

0

0x0106

262

RW

100% value for analog output 1

signed integer, -32000...+32000 (ppm / ‰)

1000

0x0107

263

RW

0% value for analog output 2

signed integer, -32000...+32000 (ppm / ‰)

0

0x0108

264

RW

100% value for analog output 2

signed integer, -32000...+32000 (ppm / ‰)

1000

 * - The new value is applied after restart.
** - Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the
only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.
*** - This value is dynamic and not kept in EEPROM after restart

L

1

2

3

4

L

H

L

L

H

H

H

L

1

2

3

4

L

H

L

L

H

H

H

Reviews: