E2648 series heavy duty detectors-transmitters belong to the PluraSens® family of
multifunctional  measurement  instruments.  The  instruments  utilise  gas  sensors  of
various  types  with  excellent  repeatability,  stability  and  long  lifetime.  Due  to  its  IP66
enclosure of die cast aluminium, the device may be used under harsh conditions.
E2648  series  provides  two  independent  analog  outputs  OUT1  and  OUT2,  user-
selectable to 4-20 mA or 0-10 V, proportional either to gas concentration or temperature.
RS485  Modbus  RTU  digital  communication  interface  allows  easy  instrument
configuration and integration into various automation systems.
The following features are available as option:

Two relays RE1 and RE2 with closing contacts. Relay outputs can be used to switch
alarm sirens, ventilation fans, shut-off valves or other actuators
Acoustic (85 dB buzzer) and visual (red and green LED) alarm
Integrated 230 V mains power supply module
Remote probe. The remote probe is connected to the main unit with shielded cable.
Default connection cable length is 3 m.

The version of your device is marked on the package.

Safety requirements

Always adhere to the safety provisions applicable in the country of use.
Do  not  perform  any  maintenance  operation  with  the  power  on.  Do  not  let  water  or
foreign objects inside the device.

Operating conditions

The device should be used in explosion-safe (non ATEX -rated) indoor areas, without
aggressive gases in the atmosphere. See Specification table for more details.

Mounting dimensions

Installation

There are no precise rules or standards to follow when installing the gas detectors. The
following points must be taken into account:

application (air quality control or leakage detection),
properties of the space under investigation (room geometry, direction and velocity of
air flows etc),
detected gas (relative density to air, whether the gas is flammable, or toxiс, or oxygen
displacing),
safety:  strong  vibrations,  mechanical  shock,  and  the  sources  of  strong
electromagnetic interference should be avoided,
the device should be accessible for maintenance and repair.

For  early  leakage  detection  install  the  sensor  as  close  as  possible  to  the  potential
leakage  sources  (flanges,  valves,  pressure  reducers,  pumps,  etc),  taking  into
consideration other points listed above. Do not locate the detector close to ventilation
openings  and strong air  currents. Avoid  the  areas  without air  circulation  (corners,

niches)  as  well.  For  general  area  monitoring  without  definite  leakage  sources,  the
detectors  should  be  distributed  evenly  in  the  room.  For  personal  safety  control  the
detectors  are  installed  in  the  breathing  zone  (at  the  height  of  the  head  of  people  or
animals).  Recommended  sensor  position  is  vertical,  pointing  downwards.  See
Installation guidelines section for more information.
The device is fixed on the wall using two holes located outside the sealed area of the
device (see dimensional drawing 

in the previous section

).

Connections

1. Unscrew four lid screws and detach the lid from the device.
2. Attach the device to the wall. (This step may be done after the step 3, consider
your convenience).
3. Use two M16 cable glands to pass the cables of the power supply and of the external
devices.  Attach  the  power  cable  to  the  device  without  turning  it  on.  Using  the
connection diagrams below, connect the analog outputs, digital interface terminals
and/or relays to the relevant devices according to your needs.

The  screwless  quick  connect  spring  terminals  on  the  E2648  series  devices  are
suitable for a wide range of wires with cross-section 0,2...1,5 mm

2

. We recommend

to strip the wire end by 8...9 mm and tin it, or to use the wire end sleeves.
To connect the wire, insert the wire end into terminal hole. To disconnect, push the
spring loaded terminal lever, pull the wire out, and release the lever.
Use twisted pair cable, e.g. LiYY TP 2×2×0,5 mm

2

 or CAT 5, to connect the device

to RS485 network. Use one pair for A and B wires and the second pair for common
0 V  and power  +U  wires  to connect  the  transmitter  to  Fieldbus  network. Respect
polarity.  Overall  length  of  all  connections  via  RS485  interface  should  not  exceed
1200 m.
The type of each analog output can be independently changed between 4-20 mA
and 0-10 V with jumpers J1 (OUT1) and J2 (OUT2).
With closed jumper the output is 0-10 V, with open jumper the output is 4-20 mA.
By  default both outputs OUT1 and OUT2 are  assigned to gas concentration. The
device has built-in temperature sensor which may be tied to any of the outputs.
The output assignments and scales can be changed by Modbus commands.
We  recommend  to  set  the  difference  between  the  upper  and  bottom  limits  of  the
output scale not narrower than 20% of detection range (for CO detectors the scales
down to 5% of range are allowed). In any case, do not set the output scale below
the tenfold resolution of the device. 
Note  The  outputs  are  not  galvanically  isolated  from  24  V  power  supply  and  share
common 0V. Allowed load resistance limits are stated in Specifications table. To power
the instrument from an external 24 VDC source, connect terminals  0V and +U to the
source. If the integrated mains power supply module is used, connect terminals L and N
to the mains.
Note Actuator short-circuits should be avoided, to protect the instrument relays use
external fuses or safety switches.
4.  Turn  on  the  power.  The  sensor  heating  up  may  take  up  to  five  minutes  after
switching  on.  A  LED  placed  on  the  PCB  of  the  device  allows  to  control  the
connection process. The LED response to different processes  is presented in the
table below.

Process

LED mode

Sensor heating period

Blinking 0.5 Hz (50% on, 50% off)

Sensor absence or malfunction

Blinking 0.5 Hz (90% off, 10% on)

Relay 1 turned on

Blinking 1 Hz (50% on, 50% off)

Relay 2 turned on

Blinking 2 Hz (50% on, 50% off)

Modbus response

The signal is modulated with short on-off pulses,
even single Modbus cycle is traceable*

Normal measurement

Continuous light

5. Make sure that the device is properly installed, the external devices connected,
power on and control LED is constantly lit. Make certain that the cable glands are
properly tightened to ensure the conformity to IP66 protection class. Place the lid
back and fix it with the screws. The device is ready to use.
It is recommended to keep the detector-transmitter powered constantly, except for
periods of maintenance and calibration, deplacement etc.

Return to default settings

To reset the device’s Slave ID, baudrate and sbit number to factory settings: proceed as
follows

1. De-energize the device
2. Connect the J3 jumper
3. Turn on the device
4. De-energize the device
5. Disconnect the J3 jumper
6. Turn on the device

OUT1

OUT2
0V

A

B

+U

J3

J1 J2

Fieldbus

Controller

Supply

Power

Control LED

Input 1 4-20 mA / 0-10 V
Input  4-20 mA / 0-10 V

0V / GND

0V

+24V

SENSOR

E2648 basic version

4 -20 mA / 0 -10 V

4 -20 mA / 0 -10 V

0V / GN D

OUT1

OUT2
0 V
A

B

R S48 5

+U = 11...3 0 VD C

RE 1

R E2

Fie ldb us

24 VDC

S

N

L

90 ...2 65 VAC

J 3

Co ntrol L ED

J1 J 2

J1: O UT1 t ype (open: 4-20 mA; closed: 0-10 V)
J : O UT  t ype

2

2

(open: 4-20 mA; closed: 0-10 V)

J : 

3 return t o fact ory settings

E2648R version with relays

M25 (sensor)

M16 (cable entry)

125

8

0

fixing hole (Ø 5mm)

fixing hole (Ø 5mm)