background image

7

dISInfectIon

When cartridge activation and recovery adjustments are complete, 

the storage tank and associated piping must be disinfected, then 

completely flushed. The steps for this are outlined below.

Locate the 3/8" OD tubing that connects to the inlet (left side) 

1. 

of the storage tank. Disconnect the end which connects to the 

elbow fitting at the processor. Measure 1 ounce of 5.25% bleach 

for every 7.5 gallons of storage tank capacity. Pour this volume of 

bleach into the tube that leads to the storage tank. Re-connect 

this tube to the elbow fitting. Apply power to the system by 

plugging the power cord into the receptacle. The booster pump 

should begin to run and fill the storage tank.
Once sufficient water has entered the storage tank (more 

2. 

than 1/4 full), demand treated water from at least one piece of 

equipment the ENVI-RO is supplying water to. Once all of the 

air has been purged, and a solid flow of water is observed, stop 

the flow at the connected equipment. Purge the air from all 

remaining pieces of connected equipment by demanding water 

from each one individually. 
Allow the storage tank to fill until the booster pump turns off. 

3. 

Allow the chlorinated water to remain in the storage tank and 

distribution piping for 10 minutes.
Unplug the power cord. Drain the storage tank by demanding 

4. 

water downstream and allow the storage tank to drain. Once the 

storage tank is empty, stop demanding water downstream.
Apply power to the system by plugging the power cord into the 

5. 

receptacle. Once sufficient water has entered the storage tank 

(more than 1/4 full), demand treated water from at least one piece 

of equipment the ENVI-RO is supplying water to. After 5 minutes, 

stop the flow at the connected equipment. Flush the lines to each 

remaining piece of connected equipment by demanding water 

from them for 2 minutes each.
Allow the storage tank to fill until the booster pumps turns off.

6. 

Unplug the power cord. Drain the storage tank by demanding 

7. 

water downstream and allow the storage tank to drain. Once the 

storage tank is empty, stop demanding water downstream 
Repeat steps 5-7 until no residual chlorine odor is detected from 

8. 

the water exiting the storage tank or connected equipment.

PlacIng enVI-ro Into SerVIce

Once the cartridges have been activated, the storage tank and 

distribution piping sanitized, the ENVI-RO can be placed into service.
During normal operation, the valves on the ENVI-RO should be in the 

following positions:

System inlet and outlet valves – open

A. 

System by-pass valves – closed.

B. 

Once the system been started-up initially, it is a good idea to 

measure the outlet water flow rate and quality to verify the system’s 

performance. The initial values should be recorded for future 

comparison to detect any changes in performance. A Performance 

Log has been provided on Page 9 to record this information.

oPeratIon

During normal operation, a continuous supply of water must be 

1. 

available to the system.
The system inlet and outlet valves must be open, the sample 

2. 

outlet and flushing valves must be closed and the drain line must 

be unrestricted.

dual outlet and blend adjuStment

The ENVI-RO system is capable of producing two water qualities, 

which are detailed below. 

The outlet marked “STEAMER” provides water directly from the 

• 

RO Membrane. The TDS of this water is very low, ideally suited 

for applications such as flash steamers and other equipment that 

“boils away” the water. This outlet requires no adjustment.
The outlet marked “COFFEE” can produce a wide range of water 

• 

qualities. It combines or “blends” two sources of water; 1) 

directly from the RO Membrane and, 2) filtered water containing 

the same level on mineral content as the raw (feed) water.  The 

following text describes the adjustment of this feature.

Open the feedwater blend valve (FBV) and dilution blend 

1. 

valve (DBV) fully. See 

figure 6

 for location of these valves.

Demand flow on the “COFFEE” line. The flowrate should 

2. 

equal the maximum expected demand of all connected 

equipment.
Access the “Coffee TDS” view screen on the controller to 

3. 

observe a real-time reading of the TDS quantity in the water 

flowing to the “COFFEE” line. 
Compare TDS value on controller to application requirement. 

4. 

If controller reading is higher than requirement, slowly close 

FBV until TDS value is met. If controller reading is lower than 

requirement, slowly close DBV until TDS value is met.

figure 6.

 RO Blend Valve Locations

Feedwater Blend 

Valve (FBV)

Dilution Blend 

Valve (DBV)

Summary of Contents for ENVI-RO

Page 1: ...increases the inlet pressure to maintain consistent permeate production plus eliminates back pressure on the permeate output This innovative approach to both boosting and eliminating back pressure al...

Page 2: ...ler Power Supply Storage Tank Wall Mount Bracket 2 MR 600 RO cartridge 3 2SR BW Cartridge 4 Parts Kit 5 Inspect the carton for damage Report any damage to freight carrier immediately and retain all pa...

Page 3: ...ectionable taste Plastic pipe or reinforced tubing are generally very good choices for RO water distribution materials The size of the product water tubing piping should be 3 8 ID minimum Distances of...

Page 4: ...alue in seconds is entered for this setting Range is 0 995 seconds in 5 second increments Use the keys to adjust this value Press Enter to save value and go to next screen Flush Int X2 This parameter...

Page 5: ...o your TDS measurement Read across that row to determine maximum recovery permeate to reject ratio and permeate reject volumes Using 2 32 oz or 1 000 ml graduated containers apply power 2 to the syste...

Page 6: ...1 321 67 9 679 751 1000 30 0 1 to 2 33 30 0 300 70 0 700 Table 2 Capillary Tube and Flush Time Selector Reject Volume per Minute Capillary Tube Flush Time in Seconds Ounces Milliliters 1 2 0 0 6 1 0 1...

Page 7: ...odor is detected from 8 the water exiting the storage tank or connected equipment Placing ENVI RO Into Service Once the cartridges have been activated the storage tank and distribution piping sanitiz...

Page 8: ...pm Dependant on Pressure volume in storage line sizes Volume Gallons Dependant on Pressure volume in storage Pressure typical 60 100 psi 4 1 6 9 bar Salt Rejection 90 minimum Recovery Varies based on...

Page 9: ...9 maintenance section Performance Log Test Date Outlet Flow ml min Drain Flow ml min Inlet Pressure Temp psi F Inlet TDS ppm STEAMER Outlet TDS ppm COFFEE Outlet TDS ppm Reduction NOTES...

Page 10: ...capacity if applicable c Low quality RO water 3 Refer to problem 1 a Refer to problem 1 a RO cartridge failure b Replace RO cartridge b Low water pressure at water 4 using equipment Tubing piping run...

Page 11: ...13 EV312827 RESTRICTOR BLUE 735 ml min 13 EV312828 RESTRICTOR WHITE 1052 ml min 13 EV312829 RESTRICTOR GREY 1577 ml min 13 EV312830 RESTRICTOR RED 125 ml min 13 EV312831 RESTRICTOR BROWN 189 ml min 1...

Page 12: ...instructions on the MR cartridge label Place a bucket under the cartridge to catch any excess water that may spill from the head Remove the old cartridge by turning the cartridge to the left until it...

Page 13: ...13 13 6 346 23 583 406 16 32 Side View Front View Top View 813 Figure 7 Dimensional Drawing...

Page 14: ...14 Figure 8 General Installation Arrangement...

Page 15: ...15 NOTES...

Page 16: ...00 942 1153 www everpure com Printed in U S A EV3128 25 Rev A SE08 For sales replacement components and service contact your Everpure dealer or Everpure LLC 1040 Muirfield Drive Hanover Park Illinois...

Reviews: