Instruction manual for POWERLINE 33 series UPS
2010/06/22
www.ever.eu
31
START (power from mains)
Proceed as follows to start a properly connected power unit:
1)
Verify if F3 and F4 safeguards are set to OFF; if not, set them to OFF.
2)
Open fuse mounts F1, F2, and F5
3)
Set safeguards F3 and F4 to ON.
4)
Wait until the device is in SUSPEND mode.
5)
In the fuse mount of the battery pack, place an appropriate fuse link (see
TECHNICAL DATA table) and close the circuit by closing the mount.
6)
In mount F5, place an appropriate fuse link and close it in order to connect the
circuit.
7)
In mount F1, place an appropriate fuse link.
8)
Close mount F1 and immediately close mount F2.
9)
Configure the power supply unit (if the initial use or to apply changes).
10) Turn the unit on using the interface (KONTROLA 1/4; UPS).
Perform steps 5 and 6 only if an additional battery pack is connected.
Once finished, the power supply unit can operate normally.
START (no power from mains)
Proceed as follows to start a properly connected power unit:
1)
Verify if F3 and F4 safeguards are set to OFF; if not, set them to OFF.
2)
Open fuse mounts F1, F2.
3)
In mount F1, place an appropriate fuse link (do not close).
4)
In mount F5, place an appropriate fuse link and close it to close the circuit.
5)
In the fuse mount of the battery pack, place an appropriate fuse link (see
TECHNICAL DATA table) and close the circuit by closing the mount.
6)
Close mount F1.
7)
Wait 10 seconds at least.
8)
Close mount F2 – batteries connected.
9)
Set safeguards F3 and F4 to ON.
10) Configure the power supply unit (if the initial use or to apply changes).
11) Turn the unit on by using the interface (KONTROLA 1/4; UPS).
Perform steps 4 and 5 only if an additional battery pack is connected.
Once finished, the power supply unit can operate normally.