Instruction manual for POWERLINE 33 series UPS
2010/06/22
www.ever.eu
28
Disconnection of modules
1.
Turn the unit off by using the interface (KONTROLA 1/4; UPS).
2.
Set safeguards F3 and F4 (item 2 Fig. 2) to OFF.
3.
Disconnect the safeguards of the main line and the BYPASS in the
room/building switching station.
4.
Disconnect safeguards F1, F2, and F5 (item 4.7 Fig. 2) in the unit and F1 and
F2 in all battery modules, by opening the fuse mounts and removing the fuse
links.
5.
Remove the connecting element caps.
6.
Disconnect the modules. The connecting cables must be fully disconnected.
7.
Secure the connecting elements by screwing the protective cap.
8.
Activate the safeguards in the switching station of the room/building.
9.
Turn the device on based on the start-up procedure (Note! Remember to set the
appropriate battery parameters (KONFIGURACJA 5/5)).
NOTE! It is forbidden to leave any unconnected cable ends. They
could be energised with a voltage level that is dangerous to health
and/or life.